Schneider Electric LV847608

Schneider Electric LV847608 MicroLogic 6.0 X, LSIG, 400-6000

MPN LV847608
Active

Schneider Electric MasterPacT MicroLogic 6.0 X electronic control unit, LV847608, LSIG protection, 400–6000 A trip range, 690 V AC, IEC 60947-2.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV847608 specifications
ParameterValue
Display typeLCD display - 128 x 96 pixels
Trip unit typeElectronic
Main product or component typeControl unit
Voltage690 V AC, +/- 10 %
Poles4
Temp operating max70 °C
Temp operating min-35 °C
Pollution degree3 conforming to IEC 60947-1
ApplicationEquipment protection, monitoring and control
Operating temperature-25...70 °C (operating) -35 °C (for start-up of product)

Product details

The Schneider Electric LV847608 is a MicroLogic 6.0 X electronic control unit for the MasterPacT range of air circuit breakers. It provides LSIG protection — long-time, short-time, instantaneous, and ground-fault — with an adjustable trip unit rating spanning 400 A to 6000 A depending on the breaker frame (MTZ1, MTZ2, or MTZ3). The unit integrates a power meter accurate to ±0.5 % for current and voltage, and ±1 % for active power and energy. It logs alarms, events, min/max values, and trip context — data a commissioning engineer pulls via Bluetooth 4.0 LE, NFC, or USB.

What the LSIG ratings mean for selectivity

LSIG gives you four independent protection curves. Long-time delay adjusts in 0.5 s steps, with a range of 12.5 to 600 s at 1.5× Ir. Short-time and ground-fault delays are adjustable, and zone selective interlocking (ZSI) is built in — so downstream faults clear without upstream tripping. For a site electrical engineer coordinating a distribution board, ZSI means you can set tighter bands and still maintain full discrimination.

Integration into a MasterPacT breaker

This control unit mounts into the breaker's electronic cradle. It supports 3P 3d, 4P 3d, 4P 3d + N/2, 4P 4d, and 4P 3d + OSN neutral protection settings. Communication ports (Bluetooth 4.0 LE, NFC, USB) let a panel OEM wireman commission protection parameters and retrieve logs without opening the front cover.

Standards and environmental limits

Designed to IEC 60947-2 (low-voltage switchgear) and IEC 60092-202 (marine electrical installations). Relative humidity tolerance of 95 % at 55 °C per IEC 60068-2-30. Altitude rating to 5000 m with voltage derating above 2000 m.

MPN