Schneider Electric LV847608 — Air Circuit Breakers

Schneider Electric LV847608 MicroLogic 6.0 X, LSIG, 400-6000

MPNLV847608
Active

Schneider Electric MasterPacT MicroLogic 6.0 X electronic control unit, LV847608, LSIG protection, 400–6000 A trip range, 690 V AC, IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LV847608 — Identification
ParameterValue
Product typeControl unit
RangeMasterPacT
ApplicationEquipment protection, monitoring and control
LV847608 — Electrical ratings
ParameterValue
Rated operational voltage (Ue)690 V AC, +/- 10 %
Network typeAC
Network frequency50/60 Hz
LV847608 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C (operating) -35 °C (for start-up of product)
Pollution degree3 conforming to IEC 60947-1
Operating altitude<= 5000 m with operational voltage derating 560 V AC
LV847608 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60092-202 EN/IEC 60947-1 EN/IEC 60255-1

Product details

The Schneider Electric LV847608 is a MicroLogic 6.0 X electronic control unit for the MasterPacT range of air circuit breakers. It provides LSIG protection — long-time, short-time, instantaneous, and ground-fault — with an adjustable trip unit rating spanning 400 A to 6000 A depending on the breaker frame (MTZ1, MTZ2, or MTZ3). The unit integrates a power meter accurate to ±0.5 % for current and voltage, and ±1 % for active power and energy. It logs alarms, events, min/max values, and trip context — data a commissioning engineer pulls via Bluetooth 4.0 LE, NFC, or USB.

What the LSIG ratings mean for selectivity

LSIG gives you four independent protection curves. Long-time delay adjusts in 0.5 s steps, with a range of 12.5 to 600 s at 1.5× Ir. Short-time and ground-fault delays are adjustable, and zone selective interlocking (ZSI) is built in — so downstream faults clear without upstream tripping. For a site electrical engineer coordinating a distribution board, ZSI means you can set tighter bands and still maintain full discrimination.

Integration into a MasterPacT breaker

This control unit mounts into the breaker's electronic cradle. It supports 3P 3d, 4P 3d, 4P 3d + N/2, 4P 4d, and 4P 3d + OSN neutral protection settings. Communication ports (Bluetooth 4.0 LE, NFC, USB) let a panel OEM wireman commission protection parameters and retrieve logs without opening the front cover.

Standards and environmental limits

Designed to IEC 60947-2 (low-voltage switchgear) and IEC 60092-202 (marine electrical installations). Relative humidity tolerance of 95 % at 55 °C per IEC 60068-2-30. Altitude rating to 5000 m with voltage derating above 2000 m.

Frequently asked questions

What protection functions does the MicroLogic 6.0 X provide?

The MicroLogic 6.0 X provides LSIG protection: long-time overload (ANSI 49), instantaneous short-circuit (ANSI 50), short-time short-circuit (ANSI 51), and ground fault (ANSI 51N). All delays are adjustable.

What is the trip unit rating range for LV847608?

The trip unit rating is adjustable and depends on the breaker frame: 400 A to 6000 A. Specific available ratings include 400 A, 600 A, 800 A, 1000 A, 1200 A, 1600 A, 2000 A, 2500 A, 3000 A, 3200 A, 3600 A, 4000 A, 5000 A, and 6000 A.

Where can I buy LV847608?

The LV847608 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.