Skip to main content
Schneider Electric LV848186

Schneider LV848186 MasterPact MTZ2 1600A 4P Circuit Breaker,

MPN LV848186
Active

Schneider Electric MasterPacT MTZ2, LV848186, fixed 4P circuit breaker, 1600 A at 40°C, 66 kA Ics at 415 V AC, Category B.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV848186 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch115 mm
Connection surface topFront Rear
Connection surface bottomFront Rear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

LV848186 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
Depth300 mm
Width537 mm
Height352 mm
Electrical life cycles10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 AC-23 A: 10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23 A: 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440/690 V AC 50/60 Hz conforming to EN/IEC 60947-3
Mechanical life cycles25000 cycles with periodic preventive maintenance
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

MasterPact MTZ2 — 1600 A, 66 kA Ics, Category B

The Schneider LV848186 is a MasterPact MTZ2 fixed-mount, 4-pole (4P) power circuit breaker rated 1600 A at 40 °C, with a service breaking capacity (Ics) of 66 kA at 415 V AC. That Ics figure equals the ultimate capacity (Icu) on this unit — meaning after clearing a 66 kA fault, the breaker is ready to be reclosed without derating. The H1 performance variant delivers 66 kA Ics across the full voltage range up to 690 V AC. Rated insulation voltage (Ui) is 1000 V AC, operational voltage (Ue) 690 V AC, and impulse withstand (Uimp) 12 kV — figures that place this breaker squarely in heavy industrial distribution, not light commercial. The 145 kA making capacity (Icm) at 415 V AC handles the inrush when closing onto a bolted fault, and the 66 kA short-time withstand (Icw) for 1 second allows delayed tripping for full selectivity coordination.

Selectivity and coordination — Category B

Category B (IEC 60947-2) is the key distinction here: this breaker is designed for selective coordination, not just individual protection. The 66 kA Icw for 1 s means downstream devices can clear a fault while the MTZ2 holds closed, avoiding a total plant blackout. For a site electrical engineer building a discrimination study, that 1-second withstand window is the parameter that governs upstream breaker sizing and cable thermal stress limits. The electrical durability is rated at 10,000 cycles at 440 V and 690 V AC under EN/IEC 60947-2, with 6,000 cycles in AC-3 motor-switching duty. Mechanical durability hits 25,000 cycles with periodic preventive maintenance — a realistic figure for a main breaker that sees infrequent switching but must be reliable when called upon.

Lifecycle and sourcing status

Compliance documentation covers EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-2 Annex H, and IEC 61557-12. Storage range is -40 to 85 °C.

Physical integration — fixed mount, 4P

Fixed-mount format on rails or base plate. Dimensions: 537 mm wide, 352 mm high, 300 mm deep. Connection pitch is 115 mm. Both front and rear connections are available on the upside and downside, giving panel builders flexibility in busbar routing and cable entry. The neutral position is on the right (standard for 4P configurations). Push-button control type, without an integral control unit — so external trip/alarm accessories or a separate control unit (e.g., Micrologic trip unit) would be specified separately for this frame. IP30 protection rating suits indoor switchgear assemblies; for dusty or damp environments, enclosure-level protection is required.

MPN