Skip to main content
Schneider Electric LV848186 — Circuit Breaker Accessories

Schneider LV848186 MasterPact MTZ2 1600A 4P Circuit Breaker,

MPNLV848186
Active

Schneider Electric MasterPacT MTZ2, LV848186, fixed 4P circuit breaker, 1600 A at 40°C, 66 kA Ics at 415 V AC, Category B.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LV848186 — Identification
ParameterValue
Product / component typeCircuit breaker
Product nameMasterPact MTZ2
Product rangeMasterPacT
Device applicationPower distribution protection

Electrical

LV848186 — Electrical
ParameterValue
Rated current [In]1600 A at 40 °C
Rated operational voltage [Ue]690 V AC 50/60 Hz
Rated insulation voltage [Ui]1000 V AC 50/60 Hz
Rated impulse withstand voltage [Uimp]12 kV
Poles description4P

Protection & Performance

LV848186 — Protection & Performance
ParameterValue
Rated service breaking capacity [Ics]66 kA at 220/415 V AC 50/60 Hz 66 kA at 440 V AC 50/60 Hz 66 kA at 500/525 V AC 50/60 Hz 66 kA at 660/690 V AC 50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Mechanical durability25000 cycles with periodic preventive maintenance
Electrical durability10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 AC-23A: 10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23A: 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440/690 V AC 50/60 Hz conforming to EN/IEC 60947-3

Mechanical

LV848186 — Mechanical
ParameterValue
Connection pitch115 mm
Downside connectionFront Rear
Upside connectionFront Rear
Device short nameMTZ2 16 H1
Control typePush-button
Mounting modeFixed
Mounting supportRails Base plate
Width537 mm
Height352 mm
Depth300 mm

Environmental

LV848186 — Environmental
ParameterValue
IP degree of protectionIP30 conforming to EN 60529
Pollution degree3 conforming to IEC 60947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-40...85 °C

Approvals

LV848186 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12

Product details

MasterPact MTZ2 — 1600 A, 66 kA Ics, Category B

The Schneider LV848186 is a MasterPact MTZ2 fixed-mount, 4-pole (4P) power circuit breaker rated 1600 A at 40 °C, with a service breaking capacity (Ics) of 66 kA at 415 V AC. That Ics figure equals the ultimate capacity (Icu) on this unit — meaning after clearing a 66 kA fault, the breaker is ready to be reclosed without derating. The H1 performance variant delivers 66 kA Ics across the full voltage range up to 690 V AC. Rated insulation voltage (Ui) is 1000 V AC, operational voltage (Ue) 690 V AC, and impulse withstand (Uimp) 12 kV — figures that place this breaker squarely in heavy industrial distribution, not light commercial. The 145 kA making capacity (Icm) at 415 V AC handles the inrush when closing onto a bolted fault, and the 66 kA short-time withstand (Icw) for 1 second allows delayed tripping for full selectivity coordination.

Selectivity and coordination — Category B

Category B (IEC 60947-2) is the key distinction here: this breaker is designed for selective coordination, not just individual protection. The 66 kA Icw for 1 s means downstream devices can clear a fault while the MTZ2 holds closed, avoiding a total plant blackout. For a site electrical engineer building a discrimination study, that 1-second withstand window is the parameter that governs upstream breaker sizing and cable thermal stress limits. The electrical durability is rated at 10,000 cycles at 440 V and 690 V AC under EN/IEC 60947-2, with 6,000 cycles in AC-3 motor-switching duty. Mechanical durability hits 25,000 cycles with periodic preventive maintenance — a realistic figure for a main breaker that sees infrequent switching but must be reliable when called upon.

Lifecycle and sourcing status

Compliance documentation covers EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-2 Annex H, and IEC 61557-12. Storage range is -40 to 85 °C.

Physical integration — fixed mount, 4P

Fixed-mount format on rails or base plate. Dimensions: 537 mm wide, 352 mm high, 300 mm deep. Connection pitch is 115 mm. Both front and rear connections are available on the upside and downside, giving panel builders flexibility in busbar routing and cable entry. The neutral position is on the right (standard for 4P configurations). Push-button control type, without an integral control unit — so external trip/alarm accessories or a separate control unit (e.g., Micrologic trip unit) would be specified separately for this frame. IP30 protection rating suits indoor switchgear assemblies; for dusty or damp environments, enclosure-level protection is required.

Frequently asked questions

Where can I buy LV848186 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for your required quantity and delivery window.

What is the closest alternative to LV848186 in the MasterPact family?

Within the MasterPact MTZ2 range, the closest alternative would be a different performance variant (e.g., H2 or) or a different rated current (e.g., 1250 A or 2000 A frame). There is no pin-compatible drop-in; the choice depends on the required Ics/Icw and selectivity study. Compare the Ics and Icw values against your fault-level study to select the correct variant.

What is LV848186's depth and overall dimensions?

Depth is 300 mm, width 537 mm, height 352 mm. Connection pitch is 115 mm. Fixed-mount format on rails or base plate.

What compliance documentation does Schneider provide for LV848186?

The breaker complies with EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-2 Annex H, and IEC 61557-12. It is suitable for isolation per EN/IEC 60947-2 and rated pollution degree 3.

MPN
LV848186