Skip to main content
Schneider Electric LV848426

Schneider Electric LV848426 MasterPact MTZ2 800A Drawout Cir

MPN LV848426
Active

Schneider Electric MasterPacT MTZ2, LV848426, drawout circuit breaker, 800 A, 4P, H2 100 kA at 415 V AC, current production.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV848426 specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch115 mm
Connection surface topFront Rear
Connection surface bottomFront Rear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
Electrical life cycles10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 AC-23 A: 10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23 A: 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440/690 V AC 50/60 Hz conforming to EN/IEC 60947-3
Mechanical life cycles25000 cycles with periodic preventive maintenance
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

The Schneider Electric LV848426 is a MasterPact MTZ2 drawout circuit breaker rated 800 A at 40 °C, 4 poles, with an H2 performance class delivering 100 kA breaking capacity at 415 V AC. It's a Category B breaker (EN/IEC 60947-2), meaning it provides selective coordination with downstream devices — the fault stays local and the rest of the bus keeps running. The drawout chassis lets you rack the breaker out for maintenance or swap without disturbing the power connections, which is standard for switchgear lineups where uptime matters.

Breaking capacity and withstand

Rated service breaking capacity (Ics) is 100 kA at 220/415 V and 440 V AC, 85 kA at 500/525 V and 660/690 V AC — that's the fault current it can clear and still be used again. Short-time withstand (Icw) is 85 kA for 0.5 s or 1 s, 50 kA for 3 s, which covers delayed-tripping coordination in a selective system. Making capacity (Icm) hits 220 kA at 415/440 V, so it can close onto a bolted fault without welding contacts.

Physical footprint and mounting

Drawout version with chassis: 403 mm deep, 556 mm wide, 439 mm high. Without chassis: 300 mm deep, 493 mm wide, 300 mm high. Mounts on rails or a base plate. Connection pitch is 115 mm. IP30 protection (EN 60529) means it's enclosed against tools and wires >2.5 mm, typical for indoor switchgear.

Durability and operating conditions

Mechanical durability is 25,000 cycles with periodic preventive maintenance. Electrical durability: 10,000 cycles at 440 V or 690 V AC (EN/IEC 60947-2), 6,000 cycles in AC-3 motor-switching duty (EN/IEC 60947-3). Maximum breaking time is 25 ms, closing response 70 ms. Power dissipation is 100 W at rated current — factor that into enclosure ventilation.

MPN