Schneider Electric MasterPacT MTZ2, LV848426, drawout circuit breaker, 800 A, 4P, H2 100 kA at 415 V AC, current production.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LV848426 — Identification
ParameterValue
Product / component typeCircuit breaker
Product nameMasterPact MTZ2
Product rangeMasterPacT
Device applicationPower distribution protection

Electrical

LV848426 — Electrical
ParameterValue
Rated current [In]800 A at 40 °C
Rated operational voltage [Ue]690 V AC 50/60 Hz
Rated insulation voltage [Ui]1000 V AC 50/60 Hz
Rated impulse withstand voltage [Uimp]12 kV
Poles description4P

Protection & Performance

LV848426 — Protection & Performance
ParameterValue
Rated service breaking capacity [Ics]100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz 85 kA at 500/525 V AC 50/60 Hz 85 kA at 660/690 V AC 50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Mechanical durability25000 cycles with periodic preventive maintenance
Electrical durability10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 AC-23A: 10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23A: 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440/690 V AC 50/60 Hz conforming to EN/IEC 60947-3

Mechanical

LV848426 — Mechanical
ParameterValue
Connection pitch115 mm
Downside connectionFront Rear
Upside connectionFront Rear
Device short nameMTZ2 08 H2
Control typePush-button
Mounting modeDrawout
Mounting supportRails Base plate
WidthDrawout circuit breaker with chassis: 556 mm Drawout circuit breaker without chassis: 493 mm
HeightDrawout circuit breaker with chassis: 439 mm Drawout circuit breaker without chassis: 300 mm
DepthDrawout circuit breaker with chassis: 403 mm Drawout circuit breaker without chassis: 300 mm

Environmental

LV848426 — Environmental
ParameterValue
IP degree of protectionIP30 conforming to EN 60529
Pollution degree3 conforming to IEC 60947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-40...85 °C

Approvals

LV848426 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12

Product details

The Schneider Electric LV848426 is a MasterPact MTZ2 drawout circuit breaker rated 800 A at 40 °C, 4 poles, with an H2 performance class delivering 100 kA breaking capacity at 415 V AC. It's a Category B breaker (EN/IEC 60947-2), meaning it provides selective coordination with downstream devices — the fault stays local and the rest of the bus keeps running. The drawout chassis lets you rack the breaker out for maintenance or swap without disturbing the power connections, which is standard for switchgear lineups where uptime matters.

Breaking capacity and withstand

Rated service breaking capacity (Ics) is 100 kA at 220/415 V and 440 V AC, 85 kA at 500/525 V and 660/690 V AC — that's the fault current it can clear and still be used again. Short-time withstand (Icw) is 85 kA for 0.5 s or 1 s, 50 kA for 3 s, which covers delayed-tripping coordination in a selective system. Making capacity (Icm) hits 220 kA at 415/440 V, so it can close onto a bolted fault without welding contacts.

Physical footprint and mounting

Drawout version with chassis: 403 mm deep, 556 mm wide, 439 mm high. Without chassis: 300 mm deep, 493 mm wide, 300 mm high. Mounts on rails or a base plate. Connection pitch is 115 mm. IP30 protection (EN 60529) means it's enclosed against tools and wires >2.5 mm, typical for indoor switchgear.

Durability and operating conditions

Mechanical durability is 25,000 cycles with periodic preventive maintenance. Electrical durability: 10,000 cycles at 440 V or 690 V AC (EN/IEC 60947-2), 6,000 cycles in AC-3 motor-switching duty (EN/IEC 60947-3). Maximum breaking time is 25 ms, closing response 70 ms. Power dissipation is 100 W at rated current — factor that into enclosure ventilation.

Frequently asked questions

What are the key ratings for LV848426?

The LV848426 is rated 800 A at 40 °C, 4 poles, H2 performance class with 100 kA breaking capacity at 415 V AC. Rated insulation voltage is 1000 V AC, operational voltage 690 V AC. Short-time withstand current is 85 kA for 1 s.

What standards does LV848426 comply with?

The LV848426 complies with EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-2 Annex H, and IEC 61557-12. It is suitable for isolation per EN/IEC 60947-2.

Where can I buy LV848426 and how is it quoted?

LV848426 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for your quantity and delivery requirements.

What are the physical dimensions of LV848426?

Drawout version with chassis: 403 mm deep, 556 mm wide, 439 mm high. Without chassis: 300 mm deep, 493 mm wide, 300 mm high.