Skip to main content
Schneider Electric LV848427

Schneider LV848427 MasterPact MTZ2 1000A Drawout Breaker, 10

MPN LV848427
Active

Schneider Electric MasterPact MTZ2 drawout circuit breaker, LV848427, 4P, 1000 A rated current, H2 100 kA breaking capacity at 415 V AC, Category B selectivity.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV848427 specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch115 mm
Connection surface topFront Rear
Connection surface bottomFront Rear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
Electrical life cycles10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 AC-23 A: 10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23 A: 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440/690 V AC 50/60 Hz conforming to EN/IEC 60947-3
Mechanical life cycles25000 cycles with periodic preventive maintenance
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

The Schneider LV848427 is a MasterPact MTZ2 drawout circuit breaker, 4-pole, rated 1000 A at 40 °C.

The H2 rating delivers 100 kA Icu at 415 V AC and 85 kA at 690 V AC. Short-time withstand (Icw) is 85 kA for 1 second, which covers delayed tripping for selective coordination. Making capacity (Icm) hits 220 kA at 415 V, handling the first asymmetric peak of a short circuit.

Drawout construction and panel integration

Drawout mounting means the breaker slides into a fixed chassis — the disconnect position isolates it for maintenance without unbolting power cables. With chassis, the unit is 403 mm deep, 556 mm wide, 439 mm tall. Without chassis, depth drops to 300 mm, width to 493 mm, height to 300 mm. Connection pitch is 115 mm; both front and rear connection are available. Mounts on rails or a base plate.

IP30 protection per EN 60529. Rated insulation voltage 1000 V AC, operational voltage 690 V AC, impulse withstand 12 kV. Electrical durability is 10,000 cycles at 440 V and 690 V AC; mechanical durability 25,000 cycles with periodic preventive maintenance.

MPN
LV848427