The Schneider LV848427 is a MasterPact MTZ2 drawout circuit breaker, 4-pole, rated 1000 A at 40 °C.
The H2 rating delivers 100 kA Icu at 415 V AC and 85 kA at 690 V AC. Short-time withstand (Icw) is 85 kA for 1 second, which covers delayed tripping for selective coordination. Making capacity (Icm) hits 220 kA at 415 V, handling the first asymmetric peak of a short circuit.
Drawout construction and panel integration
Drawout mounting means the breaker slides into a fixed chassis — the disconnect position isolates it for maintenance without unbolting power cables. With chassis, the unit is 403 mm deep, 556 mm wide, 439 mm tall. Without chassis, depth drops to 300 mm, width to 493 mm, height to 300 mm. Connection pitch is 115 mm; both front and rear connection are available. Mounts on rails or a base plate.
IP30 protection per EN 60529. Rated insulation voltage 1000 V AC, operational voltage 690 V AC, impulse withstand 12 kV. Electrical durability is 10,000 cycles at 440 V and 690 V AC; mechanical durability 25,000 cycles with periodic preventive maintenance.