Skip to main content
Schneider Electric LV848498WW

LV848498WW MicroLogic 2.0 Xi Control Unit, MasterPacT, 690 V

MPN LV848498WW
Obsolete

Schneider Electric MasterPacT series, MicroLogic 2.0 Xi electronic control unit, LI protection, 690 V AC, drawout mounting.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV848498WW specifications
ParameterValue
Control typeWired control
Display typeLCD display - 128 x 96 pixels
Trip unit typeElectronic
Main product or component typeControl unit
Voltage690 V AC, +/- 10 %
Poles4
Temp operating max70 °C
Temp operating min-35 °C
Pollution degree3 conforming to IEC 60947-1
ApplicationEquipment protection, monitoring and control
Operating temperature-25...70 °C (operating) -35 °C (for start-up of product)

Product details

The LV848498WW is a Schneider Electric MicroLogic 2.0 Xi electronic control unit for MasterPacT air circuit breakers. It is a wired-control device with an LCD display (128 x 96 pixels) and provides equipment protection, monitoring, and control for distribution networks at 50/60 Hz. The trip unit offers LI protection — long-time overload (ANSI 49) and instantaneous short-circuit (ANSI 50) — with adjustable long-time delay in 0.5 s steps and electronic thermal memory. It is rated for operational voltages up to 690 V AC (+/- 10 %).

Fit and mounting — what the drawout form factor means for your panel

This control unit is a drawout-mounted module, meaning it plugs into the MasterPacT breaker cradle and can be removed without disturbing the main power wiring — useful for panel access, retrofit, or swap-out during a line changeover. Pole configurations supported are 3P 3d, 4P 3d, 4P 3d + N/2, 4P 4d, and 4P 3d + OSN, with neutral protection settings selectable per the configuration. Trip unit ratings cover a wide band from 400 A through 6300 A, so the same control unit board can serve multiple breaker frame sizes with the appropriate sensor.

The LV848498WW integrates a power meter measuring current (I1, I2, I3, Iavg, IN RMS, Ig RMS), voltage (phase-to-phase and phase-to-neutral), active/reactive/apparent power and energy, power factor, frequency, THD, and unbalance. Accuracy is Class 0.5 for voltage unbalance, Class 1 for active energy, and Class 2 for THD(V). For MTZ1 frames, current accuracy is +/- 0.5 % from 40 to 1600 x 1.2 A. Measurement voltage range is 208...828 V AC phase-to-phase, 120...480 V AC phase-to-neutral, with a frequency measurement range of 40...70 Hz. The measurement category is IV per IEC 61010-2-30, suitable for utility-side metering at the service entrance.

Compliance and environmental — what documentation supports qualification

The control unit complies with EN/IEC 60947-2 (circuit-breakers), EN/IEC 60092-202 (marine), EN/IEC 60947-1, EN/IEC 60255-1 (measuring relays), and EN/IEC 61010-1 (safety). EMC immunity covers electrostatic discharge, electromagnetic fields, fast transients, surge (1.2/50 µs), conducted RF, and conducted/radiated emissions Class A per CISPR 22. Overvoltage category IV per IEC 61010-1. Relative humidity rating is 95 % at 55 °C per IEC 60068-2-30. Operating altitude is up to 5000 m with voltage derating to 560 V AC. Note: the unit is not approved for wet locations per IEC 61010-1.

MPN