Skip to main content
Schneider Electric LX1G3RLSEN

Schneider LX1G3RLSEN Contactor Coil, TeSys Giga

MPN LX1G3RLSEN
Active

Schneider Electric TeSys Giga LX1G3RLSEN contactor coil, 200-500V AC/DC control voltage, 3-pole, built-in bidirectional peak limiting, IP20, active production.

$280.00 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LX1G3RLSEN specifications
ParameterValue
Main product or component typeContactor coil
Coil voltage200...500 V AC/DC 50/60 Hz
IP ratingIP20
Temp storage max80 °C
Temp storage min-60 °C
Temp operating max60 °C
Temp operating min-25 °C
Storage temperature-76...176 °F (-60...80 °C)
Pollution degree3 IEC 60947-1
Depth3.7 in (93.0 mm)
Width5.5 in (140.0 mm)
Height6.6 in (167.0 mm)
Mechanical life cycles5 Mcycles
Operating time20...35 ms opening 40...55 ms closing
Operating temperature-13...140 °F (-25...60 °C)
Permissible ambient air temperature around the device-40...158 °F (-40...70 °C) at Uc

Product details

Coil for LC1G265-330/3P — control voltage and mating pair

The LX1G3RLSEN is the control module for the TeSys Giga LC1G265-330/3P standard contactor — it is not a standalone coil but the plug-on electronic control block that mates with those frame sizes. The 200...500 V AC/DC control circuit voltage covers both 240 V and 480 V control panels without a separate transformer tap. Built-in bidirectional peak limiting replaces the need for external varistor or RC snubber networks on the coil — the electronics handle the inductive kick internally, which simplifies panel wiring and reduces component count per starter.

Power draw and thermal budget

Inrush is 300 W / 530 VA for the 20...35 ms opening and 40...55 ms closing stroke; once sealed, hold-in drops to 9 W / 16.1 VA. That low sealed power means the coil runs cool inside a crowded enclosure — the 5 Mcycle mechanical durability rating is realistic at the rated 600 cycles/minute maximum at 140 °F (60 °C). Push-in terminals on the control circuit accept solid or stranded wire from AWG 26 to AWG 12 (0.2...2.5 mm²) without ferrules, or flexible with ferrules down to AWG 24. The dual termination points let you loop the control voltage through multiple coils without a separate terminal block.

Standards and environmental limits

Listed to EN/IEC 60947-4-1, UL 60947-4-1A, and CSA C22.2 No 60947-4-1 — the contactor standard for motor starters and controllers. Pollution degree 3 per IEC 60947-1 means it is rated for the conductive dust and humidity typical in industrial panels, not just clean-room environments. Operating altitude is 3000 m without derating, 5000 m with a derating factor. Ambient operation spans -25 °C to +60 °C, with storage from -60 °C to +80 °C. The IP20 finger-safe housing protects against accidental contact during maintenance.

Sourcing and lifecycle

Sourced to order against the BOM quantity through authorized distribution channels.

MPN
LX1G3RLSEN