Skip to main content
Schneider Electric LX9FL933

TeSys LX9FL933 Contactor Coil, 264-299 V DC, Low Consumption

MPN LX9FL933
Active

TeSys F specific contactor coil, LX9FL933, 264..299 V DC low consumption, 48 W hold-in, 733 W inrush.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LX9FL933 specifications
ParameterValue
Control circuit typeAC 40...400 Hz low consumption DC low consumption
Main product or component typeSpecific contactor coil
Coil voltage264...299 V DC
Temp operating max55 °C
Temp operating min-5 °C
Mechanical life cycles5 Mcycles
Operating time60 ms opening 20 ms closing
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX9FL933 is a specific replacement coil for the TeSys F contactor range. It's the part that pulls the contactor in and holds it closed — no built-in suppressor, so you add the RC snubber or varistor externally based on your panel's noise environment. Rated for 264...299 V DC control voltage, with an operational range of 0.85...1.1 Uc at 131 °F (55 °C) and drop-out between 0.3...0.5 Uc. That means it'll hold in down to about 224 V DC and drop out cleanly between 79 and 132 V DC — useful to know if your DC bus sags under load. The coil draws 733 W inrush at 68 °F (20 °C) to pull the armature in, then settles to 48 W hold-in power. Heat dissipation runs 22.8...27.8 W once seated — that's the continuous thermal load the enclosure has to shed, so factor it into your panel's thermal budget.

Switching performance and duty cycle

Opening time is 60 ms, closing time is 20 ms. That's fast enough for most motor-start and isolation duties on a process line. Maximum operating rate is 1800 cycles per hour at 158 °F (70 °C) — about one cycle every two seconds, which covers high-speed indexing applications. Mechanical durability is rated at 5 million cycles. That's the mechanical life of the coil assembly itself — the contactor's electrical life will depend on the load it's switching (resistive vs motor), but the coil won't be the weak link in most installations.

MPN