Skip to main content
Schneider Electric MGN60512

MGN60512 C60N MCB, 1P D-Curve 16A, 10kA, Multi9

MPN MGN60512
Obsolete

Schneider Electric Multi9 C60N series, MGN60512 miniature circuit breaker, 1-pole, D-curve, 16 A rated, 10 kA breaking capacity at 240 V AC, DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN60512 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage240 V AC 50/60 Hz phase to neutral
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max80 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-30 °C
Storage temperature-40...80 °C
Pollution degree3 conforming to EN/IEC 60947-2

All specifications

MGN60512 additional specifications
ParameterValue
Depth73 mm
Width18 mm
Height81 mm
Electrical life cycles10000 cycles conforming to EN/IEC 60947-2
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-30...70 °C

Product details

The MGN60512 is a C60N miniature circuit breaker from the Multi9 range — a 1-pole, D-curve unit rated 16 A at 50 °C per EN/IEC 60947-2. It breaks 10 kA at 240 V AC phase-to-neutral, with a service breaking capacity (Ics) of 7.5 kA at that voltage. It mounts on a 35 mm symmetrical DIN rail, occupies 2 x 9 mm pitches (18 mm wide), and comes with tunnel-type terminals accepting 1…25 mm² rigid or flexible cable. The kit is complete: toggle control, ON/OFF indication, and a contact position indicator are all integrated.

D-curve selectivity and coordination

The D-curve (12 x In magnetic trip) is the key difference from a C-curve (5-10 x In) or B-curve (3-5 x In) MCB. For a 16 A breaker, the magnetic trip kicks in between 153.6 A and 192 A. That headroom lets you coordinate downstream with standard C-curve MCBs on lighting or general-purpose circuits — the D-curve holds through the motor start transient, then clears a hard fault upstream. Pair it with a C60N C-curve on the load side and you get selective coordination for most branch-circuit faults without oversizing the feeder breaker.

Panel integration checklist

Snaps onto 35 mm symmetrical DIN rail. Width is 18 mm (2 x 9 mm pitches) — plan the enclosure fill factor accordingly. Ambient operating range -30…70 °C, storage -40…80 °C. Earth-leakage protection requires a separate block (not integrated).

Suitable for isolation per that standard — the contact position indicator confirms open/closed state. Electrical durability 10,000 cycles, mechanical 20,000 cycles. Service breaking capacity Ics is 75 % of Icu at each voltage level.

MPN
MGN60512