Skip to main content
Schneider Electric MGN60625

MGN60625 C60H MCB, 6 A C-curve 2P, 30 kA breaking capacity

MPN MGN60625
Obsolete

Schneider Electric Multi9 C60H series, MGN60625 miniature circuit-breaker, 6 A rated current, C curve, 2 poles, 30 kA Icu at 240 V AC, 35 mm DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN60625 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase 415 V AC 50/60 Hz phase to phase
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max80 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-30 °C
Storage temperature-40...80 °C
Pollution degree3 conforming to EN/IEC 60947-2

All specifications

MGN60625 additional specifications
ParameterValue
Depth73 mm
Width36 mm
Height81 mm
Electrical life cycles10000 cycles conforming to EN/IEC 60947-2
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-30...70 °C

Product details

The MGN60625 is a C60H miniature circuit-breaker from the Multi9 range, rated 6 A with a C curve and 2 poles. It breaks up to 30 kA Icu at 240 V AC phase-to-phase per EN/IEC 60947-2, which means it handles high fault currents typical in distribution panels without upstream coordination headaches. The 35 mm symmetrical DIN-rail mount and 36 mm width (2 x 18 mm pitches) fit standard panel layouts — that's another SKU that drops right into a populated enclosure.

Rated 6 A at 50 °C per EN/IEC 60947-2, so it protects a 6 A branch circuit without derating at typical panel ambient. The C curve (magnetic trip at 8.5 x In ±20 %) suits moderate inrush loads like small motor starters or lighting contactors — it won't nuisance-trip on a 30 A cold-start surge but clears a dead short fast. Breaking capacity of 30 kA Icu at 240 V AC means it safely interrupts a fault up to that level; the service breaking capacity Ics is 15 kA (50 %) at the same voltage, so it can be reclosed after a fault within that range. Thermal-magnetic trip unit, 10,000 electrical cycles, 20,000 mechanical — solid for a distribution MCB.

Tunnel terminals accept 1 to 25 mm² rigid or flexible (with or without ferrule), torque to 2 N·m. Wire strip length 14 mm. Comb busbar compatible top or bottom. IP20 finger-safe front. The ON/OFF toggle gives local indication — no separate aux contact needed for panel status.

MPN