The MGN60625 is a C60H miniature circuit-breaker from the Multi9 range, rated 6 A with a C curve and 2 poles. It breaks up to 30 kA Icu at 240 V AC phase-to-phase per EN/IEC 60947-2, which means it handles high fault currents typical in distribution panels without upstream coordination headaches. The 35 mm symmetrical DIN-rail mount and 36 mm width (2 x 18 mm pitches) fit standard panel layouts — that's another SKU that drops right into a populated enclosure.
Rated 6 A at 50 °C per EN/IEC 60947-2, so it protects a 6 A branch circuit without derating at typical panel ambient. The C curve (magnetic trip at 8.5 x In ±20 %) suits moderate inrush loads like small motor starters or lighting contactors — it won't nuisance-trip on a 30 A cold-start surge but clears a dead short fast. Breaking capacity of 30 kA Icu at 240 V AC means it safely interrupts a fault up to that level; the service breaking capacity Ics is 15 kA (50 %) at the same voltage, so it can be reclosed after a fault within that range. Thermal-magnetic trip unit, 10,000 electrical cycles, 20,000 mechanical — solid for a distribution MCB.
Tunnel terminals accept 1 to 25 mm² rigid or flexible (with or without ferrule), torque to 2 N·m. Wire strip length 14 mm. Comb busbar compatible top or bottom. IP20 finger-safe front. The ON/OFF toggle gives local indication — no separate aux contact needed for panel status.