Schneider Electric MGN60625 — 2-Pole MCB (DIN Rail)

MGN60625 C60H MCB, 6 A C-curve 2P, 30 kA breaking capacity

MPNMGN60625
Obsolete

Schneider Electric Multi9 C60H series, MGN60625 miniature circuit-breaker, 6 A rated current, C curve, 2 poles, 30 kA Icu at 240 V AC, 35 mm DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN60625 — Identification
ParameterValue
Product nameC60
Product rangeC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
MGN60625 — Electrical
ParameterValue
Rated current [In]6 A at 50 °C conforming to EN/IEC 60947-2
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase 415 V AC 50/60 Hz phase to phase
Network type (AC/DC)DC
MGN60625 — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit8.5 x In +/- 20 %
Breaking capacity (Icu)30 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 25 kA Icu at 125 V DC phase to phase conforming to EN/IEC 60947-2
Rated service breaking capacity [Ics]15 kA 50 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 25 kA 100 % conforming to EN/IEC 60947-2 - 125 V DC
Suitable for isolationYes conforming to EN/IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
MGN60625 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Terminal tightening torquePower circuit: 2 N.m
Comb busbar / distribution block compatibilityTop or bottom: YES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
MGN60625 — Environmental
ParameterValue
Operating temperature range-30...70 °C
Storage temperature range-40...80 °C
MGN60625 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2

Product details

The MGN60625 is a C60H miniature circuit-breaker from the Multi9 range, rated 6 A with a C curve and 2 poles. It breaks up to 30 kA Icu at 240 V AC phase-to-phase per EN/IEC 60947-2, which means it handles high fault currents typical in distribution panels without upstream coordination headaches. The 35 mm symmetrical DIN-rail mount and 36 mm width (2 x 18 mm pitches) fit standard panel layouts — that's another SKU that drops right into a populated enclosure.

Rated 6 A at 50 °C per EN/IEC 60947-2, so it protects a 6 A branch circuit without derating at typical panel ambient. The C curve (magnetic trip at 8.5 x In ±20 %) suits moderate inrush loads like small motor starters or lighting contactors — it won't nuisance-trip on a 30 A cold-start surge but clears a dead short fast. Breaking capacity of 30 kA Icu at 240 V AC means it safely interrupts a fault up to that level; the service breaking capacity Ics is 15 kA (50 %) at the same voltage, so it can be reclosed after a fault within that range. Thermal-magnetic trip unit, 10,000 electrical cycles, 20,000 mechanical — solid for a distribution MCB.

Tunnel terminals accept 1 to 25 mm² rigid or flexible (with or without ferrule), torque to 2 N·m. Wire strip length 14 mm. Comb busbar compatible top or bottom. IP20 finger-safe front. The ON/OFF toggle gives local indication — no separate aux contact needed for panel status.

Frequently asked questions

Where can I buy MGN60625?

Sourced to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

What is the breaking capacity of MGN60625?

30 kA Icu at 240 V AC phase-to-phase per EN/IEC 60947-2, with 15 kA Ics (50 %) at the same voltage.

What curve and poles does MGN60625 have?

C curve, 2 poles (2P). Magnetic trip at 8.5 x In ±20 %.

What standards does MGN60625 comply with?

EN/IEC 60947-2, pollution degree 3, suitability for isolation per that standard.

MPN
MGN60625