Skip to main content
Schneider Electric MGN60866

MGN60866 C60N MCB, 1P 6A C-curve, 10 kA, Multi9

MPN MGN60866
Obsolete

Schneider Electric Multi9 C60N, MGN60866, 1-pole 6 A miniature circuit breaker, C-curve, 10 kA breaking capacity at 240 V AC, 35 mm DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN60866 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage240 V AC 50/60 Hz phase to neutral
Breaking capacity10 kA Icu at 240 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2 3 kA Icu at 415 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max80 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-30 °C
Storage temperature-40...80 °C

All specifications

MGN60866 additional specifications
ParameterValue
Pollution degree3 conforming to EN/IEC 60947-2
Depth73 mm
Width18 mm
Height81 mm
Electrical life cycles10000 cycles conforming to EN/IEC 60947-2
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-30...70 °C

Product details

The MGN60866 is a Schneider Electric C60N miniature circuit breaker from the Multi9 range, rated 6 A at 50 °C with a C-curve trip characteristic. The 10 kA Icu breaking capacity at 240 V AC phase-to-neutral (per EN/IEC 60947-2) covers most residential and light commercial fault levels; the 3 kA rating at 415 V AC is the ceiling for three-phase line-to-neutral faults.

The C-curve magnetic trip triggers at 8.5 x In ±20 %, so this 6 A breaker holds through motor inrush and capacitive loads that a B-curve would nuisance-trip on, but clears faster than a D-curve for general distribution.

Tightening torque for power circuit terminals is 2 N.m; strip length 14 mm. IP20 finger-safe terminals suit enclosed panels. Compatible with comb busbars and distribution blocks on top or bottom for multi-pole ganging.

MPN
MGN60866