Skip to main content
Schneider Electric MGN61820

Schneider MGN61820 Multi9 C60H-DC MCB, 32 A, 2P, DC, Curve B

MPN MGN61820
Obsolete

Schneider Electric Multi9 C60H-DC, MGN61820, miniature circuit breaker, 2-pole DC, 32 A rated current, curve B, 20 kA breaking capacity at 220 V DC, clip-on DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN61820 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage250 V DC 500 V DC 220 V DC 440 V DC
Insulation voltage ui500 V DC conforming to EN/IEC 60947-2
Breaking capacity20 kA Icu at 220 V DC conforming to EN/IEC 60947-2 20 kA Icu at 250 V DC conforming to EN/IEC 60947-2 10 kA Icu at 440 V DC conforming to EN/IEC 60947-2 6 kA Icu at 500 V DC conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C

All specifications

MGN61820 additional specifications
ParameterValue
Pollution degree3 conforming to EN 60947-2
ColorGrey
Depth73 mm
Width36 mm
Height81 mm
Electrical life cycles3000 cycles L/R = 2 ms
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

DC-rated miniature circuit breaker for distribution panels

The Schneider Electric MGN61820 is a Multi9 C60H-DC miniature circuit breaker rated 32 A at 50 °C (EN/IEC 60947-2), two poles, curve B, built for DC networks. The thermal-magnetic trip unit uses a curve B magnetic threshold of 5.5 x In (176 A), so it clears short-circuit faults fast while riding through moderate inrush from DC loads like contactor coils or LED drivers. The IP20 finger-safe front and IP40 modular enclosure rating allow installation in distribution boards with gland plates — no extra shrouding needed for panel-side access.

The MGN61820 carries four DC breaking-capacity ratings: 20 kA at 220 V DC, 20 kA at 250 V DC, 10 kA at 440 V DC, and 6 kA at 500 V DC. The 250 V DC rating matches the most common nominal voltage for 2-pole DC distribution (two 125 V batteries in series, or a 250 V solar string). The 440 V DC and 500 V DC ratings cover higher-voltage arrays or traction battery banks — but the available fault current must stay under 10 kA or 6 kA respectively. Rated operational voltages are 220 / 250 / 440 / 500 V DC; rated insulation voltage is 500 V DC.

Integration notes

Tunnel-type terminals accept 1…35 mm² rigid stranded (AWG 18…2) or 1…25 mm² flexible. Strip length 14 mm, torque to 3.5 N·m. Padlockable toggle for LOTO compliance. Tropicalisation class 2 per IEC 60068-2 for humid environments.

MPN
MGN61820