Skip to main content
Schneider Electric MGN61820 — 2-Pole MCB (DIN Rail)

Schneider MGN61820 Multi9 C60H-DC MCB, 32 A, 2P, DC, Curve B

MPNMGN61820
Obsolete

Schneider Electric Multi9 C60H-DC, MGN61820, miniature circuit breaker, 2-pole DC, 32 A rated current, curve B, 20 kA breaking capacity at 220 V DC, clip-on DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

MGN61820 — Identification
ParameterValue
Product nameMulti9 C60H-DC
Series / familyMulti9
Device short nameC60H-DC
Product / component typeMiniature circuit-breaker
Device applicationDistribution
MGN61820 — Electrical
ParameterValue
Rated current [In]32 A at 50 °C conforming to EN/IEC 60947-2
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]250 V DC 500 V DC 220 V DC 440 V DC
Network type (AC/DC)DC
MGN61820 — Protection
ParameterValue
Tripping curve codeB
Magnetic tripping limit5.5 x In +/- 20 % DC
Breaking capacity (Icu)20 kA Icu at 220 V DC conforming to EN/IEC 60947-2 20 kA Icu at 250 V DC conforming to EN/IEC 60947-2 10 kA Icu at 440 V DC conforming to EN/IEC 60947-2 6 kA Icu at 500 V DC conforming to EN/IEC 60947-2
Rated service breaking capacity [Ics]15 kA 75 % conforming to EN/IEC 60947-2 - 220 V DC 15 kA 75 % conforming to EN/IEC 60947-2 - 250 V DC 7.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V DC 4.5 kA 75 % conforming to EN/IEC 60947-2 - 500 V
Suitable for isolationYes conforming to EN/IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
MGN61820 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height81 mm
Depth73 mm
Mounting supportDIN rail
Mounting modeClip-on
Terminal connectionsTunnel type terminal (top or bottom)1...35 mm² (AWG 18...AWG 2) - rigid stranded Tunnel type terminal (top or bottom)1...25 mm² (AWG 18...AWG 4) - flexible Tunnel type terminal (top or bottom)1...25 mm² (AWG 18...AWG 4) - flexible with ferrule Tunnel type terminal (top or bottom) - 2 cable(s) 1...16 mm² (AWG 18...AWG 6) - rigid stranded Tunnel type terminal (top or bottom) - 2 cable(s) 1...16 mm² (AWG 18...AWG 6) - flexible Tunnel type terminal (top or bottom) - 2 cable(s) 1...16 mm² (AWG 18...AWG 6) - flexible with ferrule Tunnel type terminal (top or bottom) - 3 cable(s) 4 mm² (AWG 6) - flexible stranded
Terminal tightening torque3.5 N.m top or bottom
Local signalling / indicationON/OFF indication
Contact position indicatorYes
MGN61820 — Environmental
ParameterValue
Operating temperature range-25...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
MGN61820 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2

Product details

DC-rated miniature circuit breaker for distribution panels

The Schneider Electric MGN61820 is a Multi9 C60H-DC miniature circuit breaker rated 32 A at 50 °C (EN/IEC 60947-2), two poles, curve B, built for DC networks. The thermal-magnetic trip unit uses a curve B magnetic threshold of 5.5 x In (176 A), so it clears short-circuit faults fast while riding through moderate inrush from DC loads like contactor coils or LED drivers. The IP20 finger-safe front and IP40 modular enclosure rating allow installation in distribution boards with gland plates — no extra shrouding needed for panel-side access.

The MGN61820 carries four DC breaking-capacity ratings: 20 kA at 220 V DC, 20 kA at 250 V DC, 10 kA at 440 V DC, and 6 kA at 500 V DC. The 250 V DC rating matches the most common nominal voltage for 2-pole DC distribution (two 125 V batteries in series, or a 250 V solar string). The 440 V DC and 500 V DC ratings cover higher-voltage arrays or traction battery banks — but the available fault current must stay under 10 kA or 6 kA respectively. Rated operational voltages are 220 / 250 / 440 / 500 V DC; rated insulation voltage is 500 V DC.

Integration notes

Tunnel-type terminals accept 1…35 mm² rigid stranded (AWG 18…2) or 1…25 mm² flexible. Strip length 14 mm, torque to 3.5 N·m. Padlockable toggle for LOTO compliance. Tropicalisation class 2 per IEC 60068-2 for humid environments.

Frequently asked questions

How do I get current pricing and availability for MGN61820?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time — the part is sourced to order through independent distribution.

What is MGN61820's breaking capacity at 220 V DC?

20 kA Icu at 220 V DC per EN/IEC 60947-2. Also rated 20 kA at 250 V DC, 10 kA at 440 V DC, and 6 kA at 500 V DC.

What does curve B mean on this DC breaker?

Curve B means the magnetic trip fires at 5.5 x In (176 A for the 32 A version) — fast enough for short-circuit protection but tolerant of moderate DC inrush.

MPN