Skip to main content
Schneider Electric MGN61823

Schneider MGN61823 Multi9 C60H-DC MCB, 63 A, 2P, Curve B, DC

MPN MGN61823
Obsolete

Schneider Electric Multi9 C60H-DC, MGN61823, miniature circuit breaker, 2-pole, 63 A, curve B, 20 kA breaking capacity at 250 V DC, EN/IEC 60947-2.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN61823 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage250 V DC 500 V DC 220 V DC 440 V DC
Insulation voltage ui500 V DC conforming to EN/IEC 60947-2
Breaking capacity20 kA Icu at 220 V DC conforming to EN/IEC 60947-2 20 kA Icu at 250 V DC conforming to EN/IEC 60947-2 10 kA Icu at 440 V DC conforming to EN/IEC 60947-2 6 kA Icu at 500 V DC conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C

All specifications

MGN61823 additional specifications
ParameterValue
Pollution degree3 conforming to EN 60947-2
ColorGrey
Depth73 mm
Width36 mm
Height81 mm
Electrical life cycles3000 cycles L/R = 2 ms
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

DC-rated MCB for distribution panels

It's a 2-pole unit rated 63 A at 50 °C with a B curve (magnetic trip at 5.5 x In +/- 20% DC). The 20 kA breaking capacity at 250 V DC means it can safely interrupt high-fault DC arcs — a different failure mode than AC, which is why this part carries its own EN/IEC 60947-2 listing.

Breaking capacity and voltage ratings

Breaking capacity varies with system voltage: 20 kA Icu at 220 V DC and 250 V DC, 10 kA at 440 V DC, and 6 kA at 500 V DC. Rated operational voltage options are 220 V DC, 250 V DC, 440 V DC, and 500 V DC. For a 250 V DC bus — common in telecom or solar combiner boxes — the full 20 kA is available. At 500 V DC the breaker still holds 6 kA, which covers most battery-bank or UPS distribution applications.

Thermal-magnetic trip and isolation suitability

The thermal-magnetic trip unit handles overloads (thermal) and short-circuits (magnetic).

Durability and environmental ratings

Mechanical durability is rated at 20,000 cycles; electrical durability at 3,000 cycles with L/R = 2 ms (a standard DC time constant). IP20 at the terminals, IP40 on the modular enclosure. Tropicalisation class 2 per IEC 60068-2 means it's treated against humidity and mould — relevant for warm, non-air-conditioned enclosures. Relative humidity tolerance is 95% at 55 °C.

Dual and triple cable entries are supported: two cables up to 16 mm² each, or three 4 mm² cables. Strip length 14 mm. The breaker is padlockable for lockout/tagout.

MPN
MGN61823