Skip to main content
Schneider Electric MGN61831

MGN61831 Multi9 C60H-DC Miniature Circuit-Breaker, 1P, 10 A,

MPN MGN61831
Obsolete

Schneider Electric Multi9 C60H-DC miniature circuit-breaker, 1P, 10 A rated current, curve C, 20 kA breaking capacity at 110 V DC, for DC networks.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN61831 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage250 V DC 110 V DC 220 V DC
Insulation voltage ui500 V DC conforming to EN/IEC 60947-2
Breaking capacity20 kA Icu at 110 V DC conforming to EN/IEC 60947-2 10 kA Icu at 220 V DC conforming to EN/IEC 60947-2 6 kA Icu at 250 V DC conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C

All specifications

MGN61831 additional specifications
ParameterValue
Pollution degree3 conforming to EN 60947-2
ColorGrey
Depth73 mm
Width18 mm
Height81 mm
Electrical life cycles3000 cycles L/R = 2 ms
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

DC-rated miniature circuit-breaker for distribution panels

The MGN61831 is a Schneider Electric Multi9 C60H-DC single-pole miniature circuit-breaker rated 10 A at 50 °C per EN/IEC 60947-2, with a C curve (magnetic trip at 8.5 x In ±20 % DC) and a breaking capacity of 20 kA Icu at 110 V DC, 10 kA at 220 V DC, and 6 kA at 250 V DC.

At 220 V DC the same breaker derates to 10 kA Icu, and at 250 V DC to 6 kA Icu. That makes it suitable for 110 V DC telecom plants (typical battery bank voltage) and 220 V DC solar strings, but not for 250 V DC circuits with fault currents above 6 kA. The thermal-magnetic trip unit (curve C) means it holds through mild inrush but trips fast on short-circuit — 8.5 x In magnetic threshold is standard for general distribution, not motor starting.

Tunnel-type terminals accept 1…25 mm² rigid stranded (AWG 18…4) or 1…16 mm² flexible with ferrule. Tightening torque is 2.5 N.m. Strip length 14 mm. IP20 finger-safe front; IP40 inside a modular enclosure. Padlockable toggle for lockout/tagout. The grey housing with ON/OFF indication is standard for the Multi9 range.

MPN
MGN61831