DC-rated miniature circuit-breaker for distribution panels
The MGN61831 is a Schneider Electric Multi9 C60H-DC single-pole miniature circuit-breaker rated 10 A at 50 °C per EN/IEC 60947-2, with a C curve (magnetic trip at 8.5 x In ±20 % DC) and a breaking capacity of 20 kA Icu at 110 V DC, 10 kA at 220 V DC, and 6 kA at 250 V DC.
At 220 V DC the same breaker derates to 10 kA Icu, and at 250 V DC to 6 kA Icu. That makes it suitable for 110 V DC telecom plants (typical battery bank voltage) and 220 V DC solar strings, but not for 250 V DC circuits with fault currents above 6 kA. The thermal-magnetic trip unit (curve C) means it holds through mild inrush but trips fast on short-circuit — 8.5 x In magnetic threshold is standard for general distribution, not motor starting.
Tunnel-type terminals accept 1…25 mm² rigid stranded (AWG 18…4) or 1…16 mm² flexible with ferrule. Tightening torque is 2.5 N.m. Strip length 14 mm. IP20 finger-safe front; IP40 inside a modular enclosure. Padlockable toggle for lockout/tagout. The grey housing with ON/OFF indication is standard for the Multi9 range.