Skip to main content
Schneider Electric MGN61861

MGN61861 Multi9 C60H-DC MCB, 1P, 4 A, Curve K, DC

MPN MGN61861
Obsolete

Schneider Electric Multi9 C60H-DC miniature circuit breaker, 1 pole, 4 A, curve K, 20 kA breaking capacity at 110 V DC, clip-on DIN rail mount, grey.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN61861 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage250 V DC 110 V DC 220 V DC
Insulation voltage ui500 V DC conforming to EN/IEC 60947-2
Breaking capacity20 kA Icu at 110 V DC conforming to EN/IEC 60947-2 10 kA Icu at 220 V DC conforming to EN/IEC 60947-2 6 kA Icu at 250 V DC conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C

All specifications

MGN61861 additional specifications
ParameterValue
Pollution degree3 conforming to EN 60947-2
ColorGrey
Depth73 mm
Width18 mm
Height81 mm
Electrical life cycles3000 cycles L/R = 2 ms
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

It's rated 4 A at 50 °C (conforming to EN/IEC 60947-2) with a K-curve magnetic trip of 12 x In ±20 % DC. That curve means it's designed for DC loads with moderate inrush — think DC power supplies, control circuits, or DC distribution panels where you need a thermal-magnetic trip but don't want nuisance trips from a short capacitive charge. The breaking capacity steps are 20 kA at 110 V DC, 10 kA at 220 V DC, and 6 kA at 250 V DC — so at 110 V it handles a serious fault without upstream coordination worries. It's a category A breaker (no intentional short-time delay), suitable for isolation, and carries an IP20 finger-safe front with IP40 inside an enclosure.

Clip-on DIN rail mount, 18 mm wide (2 x 9 mm pitches), 81 mm tall, 73 mm deep. It's a single-module footprint — standard for a 1P MCB. Tunnel-type terminals top and bottom accept up to 25 mm² rigid stranded, or 16 mm² flexible, with a 14 mm strip length and 2.5 N·m torque. You can land up to three 1 mm² flexible conductors per terminal if you're daisy-chaining. Pollution degree 3 means it's rated for industrial environments with conductive pollution, and tropicalisation class 2 (per IEC 60068-2) handles humidity up to 95 % at 55 °C. The toggle gives clear ON/OFF indication, and the contact position indicator confirms isolation visually. Padlockable for lockout/tagout.

MPN