Skip to main content
Schneider Electric MGN61863

Schneider MGN61863 Multi9 C60H-DC MCB, 1P, 6 A, Curve K, DC

MPN MGN61863
Obsolete

Schneider Electric Multi9 C60H-DC, miniature circuit breaker, 1-pole, 6 A, curve K, 20 kA Icu at 110 V DC, clip-on DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN61863 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage250 V DC 110 V DC 220 V DC
Insulation voltage ui500 V DC conforming to EN/IEC 60947-2
Breaking capacity20 kA Icu at 110 V DC conforming to EN/IEC 60947-2 10 kA Icu at 220 V DC conforming to EN/IEC 60947-2 6 kA Icu at 250 V DC conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C

All specifications

MGN61863 additional specifications
ParameterValue
Pollution degree3 conforming to EN 60947-2
ColorGrey
Depth73 mm
Width18 mm
Height81 mm
Electrical life cycles3000 cycles L/R = 2 ms
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

DC-rated miniature circuit breaker for distribution panels

The Schneider Electric MGN61863 is a Multi9 C60H-DC miniature circuit breaker, 1-pole, rated 6 A at 50 °C per EN/IEC 60947-2. It's built for DC networks — 250 V DC max operational voltage, with a breaking capacity of 20 kA Icu at 110 V DC, 10 kA at 220 V DC, and 6 kA at 250 V DC. The K-curve magnetic trip triggers at 12 x In (±20 %), which suits DC loads with moderate inrush — think solenoids, contactor coils, or control transformers in a 24 V or 110 V DC distribution panel. Clip it onto a DIN rail (18 mm per pole, 2 pitches wide) and terminate with tunnel-type terminals accepting up to 25 mm² rigid stranded. The IP20 finger-safe front and IP40 modular enclosure keep it panel-ready. Padlockable toggle for lockout/tagout.

The K-curve (12 x In magnetic trip) is the key difference from a B-curve or C-curve: it allows higher inrush without nuisance trips, which is why DC control circuits and solenoid loads spec K-curve.

Integration into a DC panel

The tunnel terminals accept a wide range of conductors: 1–25 mm² rigid stranded, 1–16 mm² flexible, and up to 3 x 1 mm² flexible stranded for daisy-chaining. Strip length is 14 mm; torque to 2.5 N.m. The ON/OFF indicator gives local visual status. Tropicalisation class 2 per IEC 60068-2 means it handles humidity up to 95 % at 55 °C — relevant for outdoor enclosures or washdown areas.