Schneider Electric MGN61863 — 1-Pole MCB (DIN Rail)

Schneider MGN61863 Multi9 C60H-DC MCB, 1P, 6 A, Curve K, DC

MPNMGN61863
Obsolete

Schneider Electric Multi9 C60H-DC, miniature circuit breaker, 1-pole, 6 A, curve K, 20 kA Icu at 110 V DC, clip-on DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

MGN61863 — Identification
ParameterValue
Product nameMulti9 C60H-DC
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60H-DC
Poles description1P
Number of protected poles1
Device applicationDistribution
MGN61863 — Electrical & Protection
ParameterValue
Rated current (In)6 A at 50 °C conforming to EN/IEC 60947-2
Rated operational voltage (Ue)250 V DC 110 V DC 220 V DC
Tripping curve codeK
Magnetic tripping limit12 x In +/- 20 % DC
Breaking capacity (Icu / AIR)20 kA Icu at 110 V DC conforming to EN/IEC 60947-2 10 kA Icu at 220 V DC conforming to EN/IEC 60947-2 6 kA Icu at 250 V DC conforming to EN/IEC 60947-2
Network type (AC/DC)DC
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
MGN61863 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminal (top or bottom)1...25 mm² (AWG 18...AWG 4) - rigid stranded Tunnel type terminal (top or bottom)1...16 mm² (AWG 18...AWG 6) - flexible Tunnel type terminal (top or bottom)1...16 mm² (AWG 18...AWG 6) - flexible with ferrule Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - rigid stranded Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - flexible Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - flexible with ferrule Tunnel type terminal (top or bottom) - 3 cable(s) 1 mm² (AWG 18) - flexible stranded
Mounting supportDIN rail
Mounting modeClip-on
Width18 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)2.5 N.m top or bottom
MGN61863 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
MGN61863 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2
MGN61863 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V DC conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

DC-rated miniature circuit breaker for distribution panels

The Schneider Electric MGN61863 is a Multi9 C60H-DC miniature circuit breaker, 1-pole, rated 6 A at 50 °C per EN/IEC 60947-2. It's built for DC networks — 250 V DC max operational voltage, with a breaking capacity of 20 kA Icu at 110 V DC, 10 kA at 220 V DC, and 6 kA at 250 V DC. The K-curve magnetic trip triggers at 12 x In (±20 %), which suits DC loads with moderate inrush — think solenoids, contactor coils, or control transformers in a 24 V or 110 V DC distribution panel. Clip it onto a DIN rail (18 mm per pole, 2 pitches wide) and terminate with tunnel-type terminals accepting up to 25 mm² rigid stranded. The IP20 finger-safe front and IP40 modular enclosure keep it panel-ready. Padlockable toggle for lockout/tagout.

The K-curve (12 x In magnetic trip) is the key difference from a B-curve or C-curve: it allows higher inrush without nuisance trips, which is why DC control circuits and solenoid loads spec K-curve.

Integration into a DC panel

The tunnel terminals accept a wide range of conductors: 1–25 mm² rigid stranded, 1–16 mm² flexible, and up to 3 x 1 mm² flexible stranded for daisy-chaining. Strip length is 14 mm; torque to 2.5 N.m. The ON/OFF indicator gives local visual status. Tropicalisation class 2 per IEC 60068-2 means it handles humidity up to 95 % at 55 °C — relevant for outdoor enclosures or washdown areas.

Frequently asked questions

What is the breaking capacity of MGN61863 at different DC voltages?

20 kA Icu at 110 V DC, 10 kA Icu at 220 V DC, and 6 kA Icu at 250 V DC, all conforming to EN/IEC 60947-2.

What curve type is MGN61863 and what does it mean?

Curve K with magnetic tripping at 12 x In (±20 %). This is designed for DC loads with moderate inrush current, such as solenoids, contactors, and control transformers, where a B or C curve might nuisance-trip.

Where can I buy MGN61863 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What compliance standards does MGN61863 meet?

Designed and tested to EN/IEC 60947-2 for miniature circuit breakers. Pollution degree 3, tropicalisation class 2 per IEC 60068-2. IP20 finger-safe front, IP40 modular enclosure.

MPN