MGN61865 Multi9 C60H-DC MCB, 1P 10A K Curve DC, 20 kA

MPN MGN61865
Obsolete

Schneider Electric Multi9 C60H-DC, MGN61865, 1-pole 10 A K-curve DC miniature circuit breaker, 20 kA breaking capacity at 110 V DC, DIN-rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN61865 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage250 V DC 110 V DC 220 V DC
Insulation voltage ui500 V DC conforming to EN/IEC 60947-2
Breaking capacity20 kA Icu at 110 V DC conforming to EN/IEC 60947-2 10 kA Icu at 220 V DC conforming to EN/IEC 60947-2 6 kA Icu at 250 V DC conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C

All specifications

MGN61865 additional specifications
ParameterValue
Pollution degree3 conforming to EN 60947-2
ColorGrey
Depth73 mm
Width18 mm
Height81 mm
Electrical life cycles3000 cycles L/R = 2 ms
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

DC-rated miniature circuit breaker for 1-pole distribution

The MGN61865 is a 1-pole 10 A miniature circuit breaker from the Multi9 C60H-DC series, designed specifically for DC networks. Rated at 10 A at 50 °C per EN/IEC 60947-2, this breaker uses a thermal-magnetic trip mechanism with a K curve — magnetic tripping occurs at 12 x In ±20% DC. The K curve is a good match for DC loads with moderate inrush, such as control transformers, solenoids, or DC power supplies, where you want the magnetic trip set high enough to avoid nuisance trips on startup but still provide short-circuit protection. Breaking capacity is rated at 20 kA Icu at 110 V DC, 10 kA at 220 V DC, and 6 kA at 250 V DC — all conforming to EN/IEC 60947-2. For a DC panel, the voltage rating and the pole count are the first things to check: a 1-pole DC breaker interrupts the line side, so the system neutral or return path must be handled separately. The 250 V DC maximum operational voltage (Ue) covers common 110 V and 220 V DC bus voltages found in industrial control, telecom, and railway auxiliary supplies.

The K curve magnetic trip threshold is 12 x In ±20% DC. This avoids tripping on inrush from DC-DC converters or capacitive loads. The utilisation category is A per EN/IEC 60947-2, meaning it is not intended for frequent switching of motor loads or for use as a main disconnect under load. It is a distribution breaker — set it and leave it, with occasional manual operation via the toggle for isolation (the part is marked as suitable for isolation per the standard).

Panel integration — DIN-rail clip-on, tunnel terminals

Mounts via clip-on to a standard DIN rail. IP20 rated (finger-safe) per IEC 60529, with IP40 in a modular enclosure. The grey housing includes an ON/OFF indicator and a padlockable toggle for lockout/tagout.