Skip to main content
Schneider Electric MGN61877

MGN61877 Multi9 C60H-DC MCB, 2P 3A DC, 20 kA

MPN MGN61877
Obsolete

Schneider Electric Multi9 C60H-DC, MGN61877, 2-pole DC miniature circuit breaker, 3 A rated current, 20 kA breaking capacity at 250 V DC, clip-on DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN61877 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage250 V DC 500 V DC 220 V DC 440 V DC
Insulation voltage ui500 V DC conforming to EN/IEC 60947-2
Breaking capacity20 kA Icu at 220 V DC conforming to EN/IEC 60947-2 20 kA Icu at 250 V DC conforming to EN/IEC 60947-2 10 kA Icu at 440 V DC conforming to EN/IEC 60947-2 6 kA Icu at 500 V DC conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C

All specifications

MGN61877 additional specifications
ParameterValue
Pollution degree3 conforming to EN 60947-2
ColorGrey
Depth73 mm
Width36 mm
Height81 mm
Electrical life cycles3000 cycles L/R = 2 ms
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

DC-rated miniature circuit breaker for 2-pole protection

The MGN61877 is a Schneider Electric Multi9 C60H-DC miniature circuit breaker — a 2-pole (2P) thermal-magnetic MCB rated at 3 A at 50 °C per EN/IEC 60947-2, designed specifically for DC networks. Its breaking capacity hits 20 kA Icu at 250 V DC and still delivers 10 kA at 440 V DC, so it handles fault currents across the common DC bus voltages found in industrial control panels, solar combiner boxes, and battery distribution.

Breaking capacity and selectivity in DC circuits

What sets this breaker apart from a standard AC-rated MCB is its DC-optimized arc extinction. The C60H-DC maintains 20 kA Icu at 220 V DC and 250 V DC, then steps down to 10 kA at 440 V DC and 6 kA at 500 V DC. That means on a 250 V DC bus — typical for telecom or UPS systems — it fully interrupts a 20 kA fault without cascading upstream. The magnetic trip threshold is fixed at 12 x In (±20 %), so it clears short-circuits fast while riding through moderate inrush.

Tightening torque is 2.5 N.m top or bottom. IP20 finger-safe on the front; IP40 inside the modular enclosure.

MPN