MGN61890 Multi9 C60H-DC MCB, 50 A, 2P, Curve K, DC

MPN MGN61890
Obsolete

Schneider Electric Multi9 C60H-DC, MGN61890, miniature circuit-breaker, 2P, 50 A, curve K, DC, 20 kA Icu at 220 V DC, clip-on DIN rail.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN61890 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage250 V DC 500 V DC 220 V DC 440 V DC
Insulation voltage ui500 V DC conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3 conforming to EN 60947-2

All specifications

MGN61890 additional specifications
ParameterValue
ColorGrey
Depth73 mm
Width36 mm
Height81 mm
Electrical life cycles3000 cycles L/R = 2 ms
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

DC-rated miniature circuit-breaker for distribution panels

The Schneider Electric MGN61890 is a Multi9 C60H-DC miniature circuit-breaker built for DC network protection in distribution applications. It carries a 50 A rated current at 50 °C per EN/IEC 60947-2, with a K-curve magnetic trip threshold of 12 x In ±20 % DC — meaning it handles moderate inrush without nuisance tripping, suited for DC motor or transformer branch circuits. Clip it onto a DIN rail in a standard 36 mm (4 x 9 mm pitches) footprint — fits a typical distribution board slot.

Breaking capacity is given at four DC voltages: 20 kA at 220 V DC, 20 kA at 250 V DC, 10 kA at 440 V DC, and 6 kA at 500 V DC. Match your system voltage to the closest column — if your fault current exceeds that number at your voltage, this breaker isn't the right choice. The thermal-magnetic trip unit is non-interchangeable; what you see is what protects the circuit.

The enclosure is IP20 (fingers) and IP40 inside a modular enclosure — fine for a distribution board, not for washdown. The toggle provides ON/OFF indication and the unit is padlockable for lockout/tagout. The contact position indicator gives visual confirmation of the state.

MPN