Schneider Electric MGN61890 — 2-Pole MCB (DIN Rail)

MGN61890 Multi9 C60H-DC MCB, 50 A, 2P, Curve K, DC

MPNMGN61890
Obsolete

Schneider Electric Multi9 C60H-DC, MGN61890, miniature circuit-breaker, 2P, 50 A, curve K, DC, 20 kA Icu at 220 V DC, clip-on DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

MGN61890 — Identification
ParameterValue
Product nameMulti9 C60H-DC
Series / familyMulti9
Device short nameC60H-DC
Product / component typeMiniature circuit-breaker
Device applicationDistribution
MGN61890 — Electrical
ParameterValue
Rated current [In]50 A at 50 °C conforming to EN/IEC 60947-2
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]250 V DC 500 V DC 220 V DC 440 V DC
Network type (AC/DC)DC
MGN61890 — Protection
ParameterValue
Tripping curve codeK
Magnetic tripping limit12 x In +/- 20 % DC
Breaking capacity (Icu)20 kA Icu at 220 V DC conforming to EN/IEC 60947-2 20 kA Icu at 250 V DC conforming to EN/IEC 60947-2 10 kA Icu at 440 V DC conforming to EN/IEC 60947-2 6 kA Icu at 500 V DC conforming to EN/IEC 60947-2
Rated service breaking capacity [Ics]15 kA 75 % conforming to EN/IEC 60947-2 - 220 V DC 15 kA 75 % conforming to EN/IEC 60947-2 - 250 V DC 7.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V DC 4.5 kA 75 % conforming to EN/IEC 60947-2 - 500 V
Suitable for isolationYes conforming to EN/IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
MGN61890 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height81 mm
Depth73 mm
Mounting supportDIN rail
Mounting modeClip-on
Terminal connectionsTunnel type terminal (top or bottom)1...35 mm² (AWG 18...AWG 2) - rigid stranded Tunnel type terminal (top or bottom)1...25 mm² (AWG 18...AWG 4) - flexible Tunnel type terminal (top or bottom)1...25 mm² (AWG 18...AWG 4) - flexible with ferrule Tunnel type terminal (top or bottom) - 2 cable(s) 1...16 mm² (AWG 18...AWG 6) - rigid stranded Tunnel type terminal (top or bottom) - 2 cable(s) 1...16 mm² (AWG 18...AWG 6) - flexible Tunnel type terminal (top or bottom) - 2 cable(s) 1...16 mm² (AWG 18...AWG 6) - flexible with ferrule Tunnel type terminal (top or bottom) - 3 cable(s) 4 mm² (AWG 6) - flexible stranded
Terminal tightening torque3.5 N.m top or bottom
Local signalling / indicationON/OFF indication
Contact position indicatorYes
MGN61890 — Environmental
ParameterValue
Operating temperature range-25...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
MGN61890 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2

Product details

DC-rated miniature circuit-breaker for distribution panels

The Schneider Electric MGN61890 is a Multi9 C60H-DC miniature circuit-breaker built for DC network protection in distribution applications. It carries a 50 A rated current at 50 °C per EN/IEC 60947-2, with a K-curve magnetic trip threshold of 12 x In ±20 % DC — meaning it handles moderate inrush without nuisance tripping, suited for DC motor or transformer branch circuits. Clip it onto a DIN rail in a standard 36 mm (4 x 9 mm pitches) footprint — fits a typical distribution board slot.

Breaking capacity is given at four DC voltages: 20 kA at 220 V DC, 20 kA at 250 V DC, 10 kA at 440 V DC, and 6 kA at 500 V DC. Match your system voltage to the closest column — if your fault current exceeds that number at your voltage, this breaker isn't the right choice. The thermal-magnetic trip unit is non-interchangeable; what you see is what protects the circuit.

The enclosure is IP20 (fingers) and IP40 inside a modular enclosure — fine for a distribution board, not for washdown. The toggle provides ON/OFF indication and the unit is padlockable for lockout/tagout. The contact position indicator gives visual confirmation of the state.

Frequently asked questions

What is the breaking capacity of MGN61890 at different DC voltages?

The MGN61890 has a breaking capacity of 20 kA Icu at 220 V DC, 20 kA Icu at 250 V DC, 10 kA Icu at 440 V DC, and 6 kA Icu at 500 V DC, all per EN/IEC 60947-2.

What does curve K mean on this DC MCB?

Curve K means the magnetic trip threshold is 12 x In ±20 % DC. This is higher than B or C curves, so the breaker tolerates moderate inrush currents from DC motors or transformers without nuisance tripping.

Where can I buy MGN61890 and how is it quoted?

The MGN61890 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quotation.

MPN