Compliance pack — what you get on paper
The TM241C24R: Marked CE, listed under UL 508, CSA C22.2 No 142 & 213, IEC 61131-2:2007, and carries marine approvals (LR, ABS, DNV, GL). Also meets ANSI/ISA 12-12-01 for Class I Division 2 hazardous locations. Pollution degree 2. The lifecycle field reads current — this isn’t a phase-out orphan; you can spec it into a BOM freeze without looking over your shoulder for an LTB window.
Panel fit — rail, plate, and the gap it needs
Width 150 mm, depth 95 mm, height 90 mm. Fastens onto a TH35-15 or TH35-7.5 DIN rail (IEC 60715) or plate-mounted with the fixing kit. Leaves 5.9 inches of rail space eaten up — plan neighboring terminals and a 24 V sensor supply draw of 400 mA. The backplane doesn’t supply the sensor loop; you pull that 24 V from the controller’s built-in sensor supply. Vibration tolerance: 3 gn at 8.4–150 Hz on the rail, half that if you panel-mount. Keep the cable glands tidy.