Skip to main content
Schneider Electric TM3DQ16U

TM3DQ16U Modicon TM3 16-Output Sink Module, 24 VDC

MPN TM3DQ16U
Active

Schneider Electric Modicon TM3, discrete output module, TM3DQ16U, 16 transistor sink outputs 24 V DC 300 mA, IP20, CE.

$128.27 – $248.46 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

TM3DQ16U specifications
ParameterValue
Main product or component typeDiscrete output module
IP ratingIP20
Maximum cable distance between devicesUnshielded cable <98.4 ft (30 m) transistor output
Temp storage max70 °C
Temp storage min-25 °C
Temp operating max35 °C
Temp operating min-10 °C
Storage temperature-13...158 °F (-25...70 °C)
Pollution degree2
Depth3.2 in (81.3 mm)
Width0.8 in (21.4 mm)
Height3.5 in (90 mm)
AWG gaugeAWG 26...AWG 16
ApplicationIndustrial Application
Discrete output logicNegative logic (sink)
Operating temperature14...95 °F (-10...35 °C) vertical installation) 14...131 °F (-10...55 °C) horizontal installation)

Product details

The TM3DQ16U is a 16-channel transistor output module in the Modicon TM3 family (current production); each channel sinks 300 mA at 24 V DC (negative logic) with voltage drop under 0.4 V. Typical backplane consumption is 5 mA at 5 V and 10 mA at 24 V.

Sink (negative) logic means the output switches the low side; the load connects between +24 V DC and the output terminal, a wiring convention standard for European PLC systems. The 300 mA per channel is suitable for pilot lights, small solenoid valves, and interface relays; for larger contactor coils, an interposing relay is needed. Response time is 450 µs typical for both turn-on and turn-off — fast enough for basic sequencing and batch step transitions in a brewery CIP skid, but not a high-speed counter or a positional servo output. Use this on the discrete valve manifold or pump start signals; keep the fast counter inputs on the CPU or a dedicated high-speed module. Isolation between each channel and the bus is rated at 500 V AC.

Mounting, wiring, and environmental limits

The module clips onto a standard 35 mm DIN rail (TH35-15 or TH35-7.5) with no tools; dimensions are 21.4 mm wide, 90 mm tall, 81.3 mm deep. The removable screw terminal block accepts AWG 26 to AWG 16 and has a 3.81 mm pitch. Cable distance from the module to the field device must stay under 30 m for unshielded cable. In a brewery expansion project where valve manifolds are scattered across the plant floor, plan the I/O drop locations accordingly. Operating temperature range is –10 to 55 °C in horizontal mounting, or –10 to 35 °C if mounted vertically; derate in warm panels near boiler houses. Each output has a green LED for status indication — essential for commissioning and troubleshooting a 16-point bundle. The module carries CE marking and complies with IEC 61131-2; pollution degree 2 is fine for dry control rooms but not for direct washdown zones (IP20 only).

Compliance documentation accompanies the module: CE marking under the Low Voltage and EMC directives, plus IEC 61131-2 for PLC I/O. If your site requires RoHS or REACH declarations, request them at RFQ time — they are typically bundled with the export certificate pack for Schneider TM3 products.

MPN
TM3DQ16U