Specifications

A9F05163 key specifications
ParameterValue
Control typeToggle
Network typeDC AC
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Insulation voltage ui500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Breaking capacity36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-35 °C

All specifications

A9F05163 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to EN/IEC 60947-2
ColorWhite
Depth78.5 mm
Width18 mm
Height91 mm
Electrical life cycles10000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-35...70 °C

Product details

The Schneider Electric A9F05163 is an Acti9 iC60 miniature circuit-breaker, 1 pole, rated 63 A with a D curve, designed for distribution applications on AC or DC networks.

Breaking capacity is specified under dual standards: 36 kA Icu at 12-60 V AC (EN/IEC 60947-2) and 6 kA Icn at 230 V AC (EN/IEC 60898-1). The 36 kA figure governs fault-clearing capability in industrial panels; the 6 kA Icn is the residential/commercial rating under the MCB standard. Rated insulation voltage (Ui) of 500 V AC and overvoltage category IV mean it is rated for main distribution panels, not just sub-circuits — suitable for service-entrance or branch feeder positions.

Strip length 14 mm. Overall dimensions: 91 mm height, 78.5 mm depth, 18 mm width — fits standard modular enclosure cutouts.

MPN