Skip to main content
Schneider Electric A9F05163 — 1-Pole MCB (DIN Rail)

Schneider Electric A9F05163 Acti9 iC60 MCB, D Curve, 63 A, 1

MPNA9F05163
Active

Schneider Electric Acti9 iC60 miniature circuit-breaker, A9F05163, 63 A rated current, D curve, 1 pole, 36 kA Icu at 12-60 V AC, DIN rail mount, white.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F05163 — Identification
ParameterValue
Product nameActi9 iC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameIC60N
Poles description1P
Number of protected poles1
Device applicationDistribution

Electrical & Protection

A9F05163 — Electrical & Protection
ParameterValue
Rated current (In)63 A
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu / AIR)36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles

Mounting & Connection

A9F05163 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeDouble terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible
Mounting supportDIN rail
Width18 mm
Height91 mm
Depth78.5 mm
Tightening torque (by circuit)3.5 N.m top or bottom

Environmental

A9F05163 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529

Approvals

A9F05163 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2 EN/IEC 60898-1

Electrical

A9F05163 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

The Schneider Electric A9F05163 is an Acti9 iC60 miniature circuit-breaker, 1 pole, rated 63 A with a D curve, designed for distribution applications on AC or DC networks.

Breaking capacity is specified under dual standards: 36 kA Icu at 12-60 V AC (EN/IEC 60947-2) and 6 kA Icn at 230 V AC (EN/IEC 60898-1). The 36 kA figure governs fault-clearing capability in industrial panels; the 6 kA Icn is the residential/commercial rating under the MCB standard. Rated insulation voltage (Ui) of 500 V AC and overvoltage category IV mean it is rated for main distribution panels, not just sub-circuits — suitable for service-entrance or branch feeder positions.

Strip length 14 mm. Overall dimensions: 91 mm height, 78.5 mm depth, 18 mm width — fits standard modular enclosure cutouts.

Frequently asked questions

What is the breaking capacity of A9F05163?

The breaking capacity is 36 kA Icu at 12-60 V AC (EN/IEC 60947-2) and 6 kA Icn at 230 V AC (EN/IEC 60898-1). For DC circuits it is 15 kA Icu at 12-60 V DC and 10 kA Icu at 60-72 V DC.

What does the D curve mean on this breaker?

The D curve sets the magnetic trip threshold at 12 x In +/- 20%, so the breaker tolerates high inrush currents typical of motors, transformers, or welding equipment without nuisance tripping.

How do I get current pricing and availability for A9F05163?

The part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quote.

What compliance documentation does A9F05163 carry?

The breaker is certified to EN/IEC 60947-2 and EN/IEC 60898-1, suitable for isolation per both standards, and rated IP20. It also meets tropicalisation class 2 per IEC 60068-1.

MPN
A9F05163