Skip to main content
Schneider Electric A9F06220

A9F06220 Acti9 iC60H MCB, 20A B-curve 2P, 42kA Icu

MPN A9F06220
Active

Schneider Electric Acti9 iC60H miniature circuit breaker, A9F06220, 20 A rated current, B-curve, 2 poles, 42 kA Icu at 12-133 V AC, DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9F06220 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Insulation voltage ui500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Breaking capacity42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-35 °C
Storage temperature-40...85 °C

All specifications

A9F06220 additional specifications
ParameterValue
Pollution degree3 conforming to EN/IEC 60947-2
ColorWhite
Depth78.5 mm
Width36 mm
Height91 mm
Electrical life cycles10000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-35...70 °C

Product details

The A9F06220 is a 20 A B-curve miniature circuit breaker from the Schneider Electric Acti9 iC60H series, 2-pole (2P) construction. The 20 A rating per pole governs the continuous load it can carry without thermal tripping under normal conditions. Breaking capacity is the headline differentiator here: 42 kA Icu at 12-133 V AC, 30 kA Icu at 220-240 V AC, 15 kA Icu at 380-415 V AC, and 10 kA Icu at 440 V AC (all per EN/IEC 60947-2). That places it in the highest category for mains-connected equipment — suitable for main distribution boards where the breaker sees the full utility-side surge environment, not just downstream sub-panels. The IP20 finger-safe terminals are standard for enclosed panel mounting; the DIN rail mount (36 mm width, 4 x 9 mm pitches) snaps into any standard 35 mm rail.

Dual standard compliance and isolation suitability

This MCB is certified to both EN/IEC 60898-1 (the domestic-standard for MCBs) and EN/IEC 60947-2 (the industrial-standard for low-voltage switchgear). The practical difference: 60898-1 governs the Icn rating (10 kA at 400 V) and is the basis for domestic-type approval marks; 60947-2 governs the Icu ratings and the utilisation category A, which allows the breaker to be used in industrial distribution where higher fault currents and different coordination requirements apply. The breaker is also marked as suitable for isolation per both standards — meaning when toggled off, it provides a visible air gap that meets the isolation requirements for safe maintenance access.

The double terminals (top and bottom) accept 1-25 mm² rigid or 1-16 mm² flexible conductors. Wire stripping length is 14 mm for both top and bottom connections. The thermal-magnetic trip unit provides both overload protection (thermal bimetal) and short-circuit protection (magnetic solenoid) in one package. Earth-leakage protection requires a separate Vigi iC60 block — not integrated into this base MCB.

Environmental and durability ratings

Relative humidity tolerance is 95 % at 55 °C. The limitation class is 3 per EN/IEC 60898-1, meaning it limits let-through energy (I²t) to a level that protects downstream cables and equipment within its rated breaking capacity.

MPN
A9F06220