Skip to main content
Schneider Electric A9F07350

A9F07350 Acti9 iC60H MCB 3P C-Curve 50 A, 42 kA Icu

MPN A9F07350
Active

Schneider Electric Acti9 iC60H, miniature circuit-breaker, 3P, 50 A, C-curve, 42 kA Icu at 133 V AC, DIN rail.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9F07350 key specifications
ParameterValue
Control typeToggle
Network typeDC AC
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Insulation voltage ui500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Breaking capacity42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-35 °C

All specifications

A9F07350 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to EN/IEC 60947-2
ColorWhite
Depth78.5 mm
Width54 mm
Height91 mm
Electrical life cycles10000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-35...70 °C

Product details

The A9F07350 is a Schneider Acti9 iC60H miniature circuit-breaker — 3-pole, 50 A rated current, C-curve trip (magnetic trip at 8 x In ±20 %). The 42 kA Icu at 133 V AC (per EN/IEC 60947-2) is the maximum fault current it can safely interrupt at that voltage; at 400 V AC the Icu drops to 15 kA, and the Icn (service breaking capacity per EN/IEC 60898-1) is 10 kA at 400 V. The thermal-magnetic trip handles overloads (thermal bimetal) and short-circuits (solenoid) in one unit — no separate block needed for those two functions, though earth-leakage protection requires a separate Vigi block. The toggle gives local on/off and a trip-indicator flag shows the breaker has tripped even if the handle is reset.

Dual-certified to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (household and similar) — so it qualifies for both commercial and light-industrial installations. The IEC 60898-1 rating is the one that gives you the 10 kA Icn at 400 V; the 60947-2 rating gives the higher Icu values for industrial duty. The brand provides standard RoHS/REACH declarations on request.

MPN
A9F07350