Skip to main content
Schneider Electric A9F07350 — Miniature Circuit Breakers (MCB)

A9F07350 Acti9 iC60H MCB 3P C-Curve 50 A, 42 kA Icu

MPNA9F07350
Active

Schneider Electric Acti9 iC60H, miniature circuit-breaker, 3P, 50 A, C-curve, 42 kA Icu at 133 V AC, DIN rail.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F07350 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F07350 — Ratings
ParameterValue
Rated current (In)50 A
Poles configuration3P
Number of protected poles3
Breaking capacity42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F07350 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F07350 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible
Terminal tightening torque3.5 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width54 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches6

Environmental

A9F07350 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F07350 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The A9F07350 is a Schneider Acti9 iC60H miniature circuit-breaker — 3-pole, 50 A rated current, C-curve trip (magnetic trip at 8 x In ±20 %). The 42 kA Icu at 133 V AC (per EN/IEC 60947-2) is the maximum fault current it can safely interrupt at that voltage; at 400 V AC the Icu drops to 15 kA, and the Icn (service breaking capacity per EN/IEC 60898-1) is 10 kA at 400 V. The thermal-magnetic trip handles overloads (thermal bimetal) and short-circuits (solenoid) in one unit — no separate block needed for those two functions, though earth-leakage protection requires a separate Vigi block. The toggle gives local on/off and a trip-indicator flag shows the breaker has tripped even if the handle is reset.

Dual-certified to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (household and similar) — so it qualifies for both commercial and light-industrial installations. The IEC 60898-1 rating is the one that gives you the 10 kA Icn at 400 V; the 60947-2 rating gives the higher Icu values for industrial duty. The brand provides standard RoHS/REACH declarations on request.

Frequently asked questions

How do I get current pricing and availability for A9F07350?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution.

What is the depth of the A9F07350?

The A9F07350 has a depth of 78.5 mm, which fits standard Acti9 enclosures and leaves room for wiring and busbar connections.

What compliance documentation does this brand provide for A9F07350?

The brand provides standard RoHS and REACH declarations on request. The part carries dual certification to EN/IEC 60947-2 and EN/IEC 60898-1.

MPN
A9F07350