Skip to main content
Schneider Electric A9Q54325

A9Q54325 Acti9 Vigi iC60 RCD, 3P, 25A, 300mA, Type A

MPN A9Q54325
Active

Schneider Electric Acti9 Vigi iC60 add-on residual current device, A9Q54325, 3P, 25 A, 300 mA, Type A, instantaneous, 230…415 V AC, DIN-rail clip-on.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9Q54325 specifications
ParameterValue
Main product or component typeAdd-on residual current device
Voltage230...415 V AC 50/60 Hz conforming to EN/IEC 61009-1 230...415 V AC 50/60 Hz conforming to EN/IEC 61009-2-1
Insulation voltage ui500 V AC 50/60 Hz conforming to IEC 60947-2
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-2
Depth73.5 mm
Width54 mm
Height91 mm
Operating temperature-25...60 °C

Product details

The A9Q54325 is a 3-pole add-on residual current device (RCD) from the Acti9 Vigi iC60 range, rated 25 A with 300 mA sensitivity and Type A earth-leakage protection. It clips onto the DIN rail alongside the matching iC60 MCB and plugs in electrically — no additional wiring between the two devices. The 73.5 mm depth keeps the assembly within the standard modular enclosure footprint (6 x 9 mm pitches).

This part is obsolete per the manufacturer. No official successor order code is listed, so a parametric cross-reference (same 3P, 25 A, 300 mA, Type A, instantaneous, Acti9 Vigi iC60 family) is the practical path for a like-for-like swap.

Mounts via clip-on to DIN rail. The IP20 body (IP40 in modular enclosure) suits panel-internal installation — not washdown or outdoor duty.

The voltage-independent residual current tripping technology means the RCD detects earth faults even if the phase voltage is lost — a useful safety margin on outgoing circuits. Impulse withstand is 250 A (8/20 µs waveform) per IEC 61009-1. The trip indicator gives local visual confirmation of RCD operation.

MPN