Skip to main content
Schneider Electric A9Q54325 — Residual Current Breakers (RCCB/RCBO)

A9Q54325 Acti9 Vigi iC60 RCD, 3P, 25A, 300mA, Type A

MPNA9Q54325
Obsolete

Schneider Electric Acti9 Vigi iC60 add-on residual current device, A9Q54325, 3P, 25 A, 300 mA, Type A, instantaneous, 230…415 V AC, DIN-rail clip-on.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9Q54325 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Local signalling / indicationTrip indicator
A9Q54325 — Electrical Ratings
ParameterValue
Rated current (In)25 A
Rated operational voltage (Ue)230...415 V AC 50/60 Hz conforming to EN/IEC 61009-1 230...415 V AC 50/60 Hz conforming to EN/IEC 61009-2-1
Poles description3P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to IEC 60947-2
Device location in systemOutgoer
A9Q54325 — Identification
ParameterValue
Product nameActi9 Vigi iC60
Product / component typeAdd-on residual current device
Product range / familyActi9
Device short nameVigi iC60
A9Q54325 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Width in 9 mm modules6
Terminal connectionsTunnel type terminal downside for 1 cable(s) 1...25 mm² rigid without cable end Tunnel type terminal downside for 1 cable(s) 1...16 mm² flexible without cable end Tunnel type terminal downside for 1 cable(s) 1...16 mm² flexible with cable end
Wire stripping length14 mm for bottom connection
Terminal tightening torque2 N.m bottom
Width54 mm
Height91 mm
Depth73.5 mm
A9Q54325 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-2
A9Q54325 — Approvals
ParameterValue
StandardsEN/IEC 61009-1 EN/IEC 61009-2-1

Product details

The A9Q54325 is a 3-pole add-on residual current device (RCD) from the Acti9 Vigi iC60 range, rated 25 A with 300 mA sensitivity and Type A earth-leakage protection. It clips onto the DIN rail alongside the matching iC60 MCB and plugs in electrically — no additional wiring between the two devices. The 73.5 mm depth keeps the assembly within the standard modular enclosure footprint (6 x 9 mm pitches).

This part is obsolete per the manufacturer. No official successor order code is listed, so a parametric cross-reference (same 3P, 25 A, 300 mA, Type A, instantaneous, Acti9 Vigi iC60 family) is the practical path for a like-for-like swap.

Mounts via clip-on to DIN rail. The IP20 body (IP40 in modular enclosure) suits panel-internal installation — not washdown or outdoor duty.

The voltage-independent residual current tripping technology means the RCD detects earth faults even if the phase voltage is lost — a useful safety margin on outgoing circuits. Impulse withstand is 250 A (8/20 µs waveform) per IEC 61009-1. The trip indicator gives local visual confirmation of RCD operation.

Frequently asked questions

What is the closest alternative to A9Q54325?

A parametric match within the same Acti9 Vigi iC60 family — 3P, 25 A, 300 mA, Type A, instantaneous — is the practical like-for-like replacement. No official successor order code is published.

What compliance standards does A9Q54325 meet?

It is certified to EN/IEC 61009-1 and EN/IEC 61009-2-1. Rated insulation voltage 500 V AC, impulse withstand 6 kV per IEC 60947-2.

Where can I buy A9Q54325?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
A9Q54325