Skip to main content
Schneider Electric ATH630C25N4Z

Schneider ATH630C25N4Z Altivar 600 VFD, 400 hp ND, 480 V

MPN ATH630C25N4Z
Active

Schneider Electric Altivar HVAC ATH600 series, ATH630C25N4Z AC drive, 400 hp normal duty / 300 hp heavy duty, 480 V, 451 A line current, cabinet mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATH630C25N4Z specifications
ParameterValue
Connector typeRJ45 and open style terminals
Main product or component typeVariable speed drive
Current451 A at 380 V (normal duty) 366 A at 480 V (normal duty) 365 A at 380 V (heavy duty) 301 A at 480 V (heavy duty)
Horsepower400 hp for normal duty 300 hp for heavy duty
Frequency50...60 Hz - 5...5 %
IP ratingIP00
Temp storage max70 °C
Temp storage min-25 °C
Temp operating max60 °C
Temp operating min-15 °C
Storage temperature-25...70 °C
Pollution degree2
Depth379.9 mm
Width598 mm
Height1195.38 mm
Data format8 bits, configurable odd, even or no parity 8 bits, no parity, 1 stop
Operating positionVertical position

Product details

400 hp at 480 V — normal and heavy duty defined

The ATH630C25N4Z is a cabinet-mount Altivar 600 drive rated 400 hp (250 kW) for normal duty and 300 hp (200 kW) for heavy duty at 480 V. The normal-duty line current is 451 A at 380 V and 366 A at 480 V; heavy duty draws 365 A at 380 V and 301 A at 480 V. Apparent power is 304.3 kVA normal duty, 250.2 kVA heavy duty.

Safety integration and EMC compliance

Built-in STO (safe torque off) function certified to SIL 3 per IEC 61508 and PL e per ISO 13849-1, so the drive can serve in safety circuits without an external safety relay for the stop function. The integrated Class C3 EMC filter meets EN/IEC 61800-3 for second-environment (industrial) installations, meaning an external filter may be needed for residential or first-environment mains.

HVAC-specific firmware and fieldbus options

The drive includes fire mode, forced fire mode, PID controller with three additional PID loops, damper control, scroll compressor management, and catch-on-the-fly — functions that match the Altivar 600's HVAC positioning. Communication options include BACnet IP, PROFINET, and Ethernet IP/Modbus TCP via option cards, plus a built-in 2-wire RS-485 with Modbus RTU and BACnet MS/TP.

MPN
ATH630C25N4Z