Skip to main content
Schneider Electric ATV1200A88406060

Schneider Electric ATV1200A88406060 AC Drive (VFD) 480V

MPN ATV1200A88406060
Active

Schneider Electric Altivar 1200 ATV1200A88406060 AC Drive (VFD) 480V, 7390 kW, 2970-3630 V supply, 30-pulse diode rectifier, floor-standing enclosure.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV1200A88406060 specifications
ParameterValue
Input type30 pulse diode rectifier bridge
Protection typeGround fault protection: drive
Coil voltage220 V
Current850 A
IP ratingIP41 / IP42 / IP31
Temp storage max60 °C
Temp storage min-10 °C
Temp operating max50 °C
Temp operating min0 °C
Storage temperature-10...60 °C
Pollution degreePollution degree 2
Depth1700 mm (standard efficiency)
Width8970 mm (standard efficiency)
Height3040 mm standard efficiency
Operating positionVertical +/- 10 degree
Operating temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)

Product details

Drive architecture and power stage

The ATV1200A88406060 is a medium-voltage AC drive rated for 7390 kW motor power, supplied from a 2970–3630 V input rail through a 30-pulse diode rectifier bridge. The 30-pulse topology cancels low-order harmonics at the input, reducing the need for external harmonic filtering on the line side. The drive is assembled in a floor-standing enclosure with separate air flows for the power cells and the phase-shifting transformer. Internal composition includes 15 power cells, medium-voltage arrestors, cooling fans, and a human-machine interface. Apparent power rating is 8840 kVA; line current is 850 A. Prospective short-circuit current withstand is 31.5 kA for 150 ms, which sets the fault-clearing requirement for the upstream protection.

Overload capability and protection

Standard overload profile: 1.2 × In for 60 s or 1.5 × In for 3 s. High overload profile: 1.5 × In for 60 s or 1.85 × In for 3 s. The drive includes integrated ground-fault protection and electrical isolation between power and control circuits. Dielectric strength between earth and power terminals is 20 kV AC. Overvoltage category II per EN/IEC 61800-5-1, pollution degree 2.

Physical footprint and installation constraints

Dimensions: 3040 mm high × 8970 mm wide × 1700 mm deep. The enclosure is grey (RAL 7032) and must be installed vertically within ±10° of true vertical. Cooling is forced convection with 90,000 m³/h airflow. Noise level is 80 dB. Ambient relative humidity range is 0–90 % (0–95 % optional). Electrical connection uses M10 bar-type screw terminals with clamping capacity for 6 × 40 mm² conductors, entry from bottom or top. An integrated EMC filter is included.

MPN