Skip to main content
Schneider Electric ATV6A0C13Q6

Schneider ATV6A0C13Q6 Altivar Process ATV600, 132 kW

MPN ATV6A0C13Q6
Active

Schneider Altivar Process ATV600, ATV6A0C13Q6, modular drive, 132 kW at 690 V normal duty (110 kW heavy duty), STO SIL3, integrated EMC C3 filter, cabinet mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV6A0C13Q6 specifications
ParameterValue
Main product or component typeVariable speed drive
Current138.0 A 690 V normal duty) 118.0 A 690 V heavy duty)
Frequency50...60 Hz - 5...5 %
Temp storage max70 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min1.1 °C
Storage temperature-40...158 °F (-40...70 °C)
Pollution degreePollution degree 2
Data format8 bits, configurable odd, even or no parity Modbus serial
Operating temperature14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor

Product details

Panel integration and communication

Cabinet-mount format with forced convection cooling. Pollution degree 2 per IEC 61800-5-1, so clean, non-conductive dust is fine, but oil mist or condensation calls for a higher degree. Communication options go into Slot A: the drive accepts Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen (RJ45, SUB-D, or screw terminals). Default serial interface is Modbus RTU on 2-wire RS-485, with baud rates from 4.8 to 38.4 kbit/s. If your PLC speaks EtherNet/IP, order the matching option card — the base unit handles Modbus TCP natively at 10/100 Mbit. Switching frequency is adjustable 2 to 4.9 kHz with derating above 4 kHz; the heavy-duty rating at 2 kHz is the safe starting point for motor thermal headroom. For acoustic noise-sensitive installations, raising it above 4 kHz costs output current capacity — check the derating curve in the manual.

The kit includes the power module, control unit, mounting hardware, and power connection set with fuses — no separate breaker or fuse holder to source for the 50 kA prospective short-circuit rating at the line terminals, as long as the supply is backed by a properly rated disconnect.

MPN
ATV6A0C13Q6