Skip to main content
Schneider Electric ATV6A0C25Q6

Schneider ATV6A0C25Q6 Altivar Process 600, 250 kW VFD

MPN ATV6A0C25Q6
Active

Schneider Electric Altivar Process ATV600 series, ATV6A0C25Q6 modular AC drive, 250 kW / 200 kW at 690 V, STO SIL 3, integrated EMC filter C3, cabinet mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV6A0C25Q6 specifications
ParameterValue
Main product or component typeVariable speed drive
Current255.0 A 690 V normal duty) 211.0 A 690 V heavy duty)
Frequency50...60 Hz - 5...5 %
Temp storage max70 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min1.1 °C
Storage temperature-40...158 °F (-40...70 °C)
Pollution degreePollution degree 2
Data format8 bits, configurable odd, even or no parity Modbus serial
Operating temperature14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor

Product details

250 kW at 690 V — normal and heavy duty ratings

The ATV6A0C25Q6 is a modular Altivar Process ATV600 drive rated 250 kW at 690 V in normal duty and 200 kW at 690 V in heavy duty. The heavy-duty rating gives the thermal headroom for constant-torque loads like conveyors or extruders; normal duty covers variable-torque pumps and fans where the overload margin is lower. Line current at 690 V is 255 A normal duty, 211 A heavy duty — this sets the minimum conductor ampacity and fuse rating for the branch circuit. The prospective line Isc is 50 kA, so the upstream protection must coordinate at or above that SCCR ceiling.

STO SIL 3 and safety integration

The drive also supports motor thermal protection, motor phase break detection, and overcurrent/overvoltage/undervoltage protection on the line and DC bus sides.

Fieldbus slots and communication options

Slot A accepts plug-in communication modules for Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, CANopen (with RJ45, SUB-D 9, or screw terminals), plus digital/analog I/O and relay extension modules. The base unit also carries dual-port Ethernet IP/Modbus TCP at 10/100 Mbit/s and a 2-wire RS 485 Modbus serial port with RTU framing.

EMC filter and installation environment

The integrated EMC filter supports 300 m motor cable runs and meets IEC 61800-3 category C3 — intended for industrial environments with a separate mains transformer, not residential or public low-voltage networks. The drive is cabinet-mount with UL type 1 or type 12 enclosure integration, pollution degree 2, and forced convection cooling.

Active production — sourcing posture

Lifecycle stage is current — no phase-out or discontinuation signal.

MPN