Skip to main content
Schneider Electric C160N42EFM

Schneider C160N42EFM ComPacT NS 1600A 4P 85kA 240V AC MCCB

MPN C160N42EFM
Active

Schneider Electric ComPacT NS new generation, C160N42EFM, 4P fixed MCCB, 1600 A at 50 °C, 85 kA Icu at 240 V AC, MicroLogic 2.0 E electronic trip unit, EN/IEC 60947-2.

$3,354.70 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C160N42EFM key specifications
ParameterValue
Control typeManually operated
Display typeLCD display
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Utilization categoryCategory B
IP ratingIP40
Terminal pitch70 mm
Connection surface topFront

All specifications

C160N42EFM additional specifications
ParameterValue
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947
Depth147 mm
Width280 mm
Height327 mm
Electrical life cycles1000 cycles at 690 V In 2000 cycles at 690 V In/2 2000 cycles at 440 V In 5000 cycles at 440 V In/2
Mechanical life cycles10000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The C160N42EFM is a 4-pole fixed-mount ComPacT NS new generation MCCB from Schneider Electric, rated 1600 A at 50 °C with an electronic MicroLogic 2.0 E trip unit that provides overload (L) and instantaneous short-circuit (I) protection. Its 85 kA Icu at 240 V AC and 50 kA at 415 V AC (per IEC 60947-2) means it can interrupt high fault currents without upstream cascading — a key spec for distribution panels where available fault current is high. The LCD display and energy-metering measurement type let you track load data directly at the breaker, which saves a panel builder from adding a separate power meter.

Trip unit and protection logic

The MicroLogic 2.0 E is an electronic trip unit with a 20-minute thermal memory — after a trip, it remembers the heat history so re-closing too soon doesn't cause nuisance tripping on a still-hot breaker. That matters on motor or transformer feeders where the load might re-energise while the internal temperature is still elevated. Protection is L (long-time overload) and I (instantaneous short-circuit); no short-time or ground-fault curve here, so it's suited for distribution rather than selective coordination downstream.

Mechanical and electrical endurance

Rated for 10,000 mechanical cycles and 1,000 electrical cycles at full rated current (690 V), with higher counts at reduced loads — 2,000 cycles at In/2 and 5,000 cycles at 440 V In/2. That's typical for a fixed-mount distribution breaker; it's not a switching device for frequent motor starts, but it handles routine isolation and fault clearing without wearing out early.

Fixed mount on a backplate, front-connected top and bottom, with a 70 mm connection pitch.

MPN
C160N42EFM