Skip to main content
Schneider Electric C25F44V250

Schneider C25F44V250 ComPacT NSX250F MCCB, 250A, 85kA Icu

MPN C25F44V250
Active

Schneider Electric ComPacT NSX series, NSX250F, 4-pole MCCB, 250 A, 85 kA Icu at 240 V AC, MicroLogic 4.2 electronic trip unit with integrated earth-leakage protection.

$1,322.27 – $2,913.84 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C25F44V250 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeEarth leakage circuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 15 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C

All specifications

C25F44V250 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width140 mm
Height161 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The Schneider Electric C25F44V250 is a ComPacT NSX250F 4-pole moulded-case circuit breaker (MCCB) from the ComPacT NSX family, fitted with a MicroLogic 4.2 electronic trip unit.

Across the voltage range it delivers 85 kA Icu at 220/240 V AC, 36 kA at 380/415 V, 35 kA at 440 V, 30 kA at 500 V, 22 kA at 525 V, and 8 kA at 660/690 V, all per IEC 60947-2. Under UL 60947-4-1 it is rated 85 kA at 240 V, 35 kA at 480 V, and 15 kA at 600 V AC. For a buyer specifying into a 415 V panel, the 36 kA Icu gives headroom above typical 25 kA or 35 kA fault levels common in commercial distribution — you can use it downstream of a transformer without worrying about cascading failure on a bolted fault. The 85 kA at 240 V also makes it suitable for 240 V delta or split-phase services where fault currents can be high.

Trip unit and protection logic

The MicroLogic 4.2 is an electronic trip unit — not a thermal-magnetic — which means it holds its trip curve tighter across ambient temperature swings and offers adjustable long-time pickup and delay. Earth-leakage protection is integrated (no external toroid or relay needed), adjustable via the IΔn rotary switch. The trip unit is rated 250 A at 40 °C; above that temperature the breaker must be derated per the manufacturer's curve, but the 40 °C baseline covers most enclosed panel environments. The electronic design also enables local signalling: a green flashing LED for ready-to-operate, red LED at 105 % Ir for overload, and orange LED at 90 % Ir as a pre-alarm.

Physical fit and installation

The breaker measures 161 mm high by 140 mm wide by 86 mm deep, with a 35 mm connection pitch. Both line and load connections are front-facing, which simplifies busbar and cable routing in a switchboard. The IK07 impact rating confirms it can withstand a 2 J impact, which covers accidental tool drops during maintenance.

MPN
C25F44V250