Skip to main content
Schneider Electric C63F44V570

Schneider Electric C63F44V570 ComPacT NSX630F MCCB, 570 A, 4

MPN C63F44V570
Active

Schneider Electric ComPacT NSX630F, MCCB, 570 A, 4P, MicroLogic 4.3 electronic trip unit, 36 kA at 415 V AC, EN/IEC 60947-2.

$2,486.39 – $5,951.34 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C63F44V570 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeEarth leakage circuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
IP ratingIP40
Terminal pitch45 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C

All specifications

C63F44V570 additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth110 mm
Width185 mm
Height255 mm
Electrical life cycles8000 cycles at 440 V In/2 4000 cycles at 440 V In 6000 cycles at 690 V In/2 2000 cycles at 690 V In
Mechanical life cycles15000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

Integrator note — ComPacT NSX630F, 570 A, 4P

The C63F44V570 is a Schneider Electric ComPacT NSX630F moulded-case circuit breaker with a 570 A electronic trip unit (MicroLogic 4.3) at 40 °C, four poles, and an F breaking-capacity code — 36 kA Icu at 415 V AC per IEC 60947-2.

Breaking capacity — what the F code means

The F breaking-capacity code gives 36 kA Icu at 380/415 V AC and 40 kA at 220/240 V AC. At 440 V it drops to 30 kA; at 525 V to 20 kA; at 690 V to 10 kA. That's the full interrupting rating per IEC 60947-2 — the breaker can clear a fault at those levels and still be reclosed. For UL 60947-4-1 applications (motor-circuit protectors), the same breaker carries 85 kA Icu at 240 V AC, 35 kA at 480 V, and 20 kA at 600 V. If your panel is UL-listed, use those numbers for the SCCR calculation.

Backplate-mounted, flat on the back, horizontal or vertical orientation. The 4-pole unit is 185 mm wide, 255 mm high, 110 mm deep — fits a standard distribution panel footprint. Front connections top and bottom; neutral on the left. Overvoltage category IV — suitable for main incoming supply. Ambient humidity 0–95 % non-condensing; altitude up to 2000 m without derating, 2000–5000 m with derating.

MPN