Skip to main content
Schneider Electric ENW24279

ENW24279 EasyPact NW Switch Disconnector, 1250 A, 4P

MPN ENW24279
Active

Schneider Electric EasyPact NW switch disconnector, ENW24279, 1250 A AC-23A, 690 V, 4 poles, drawout rail mount, right neutral, IP40.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24279 key specifications
ParameterValue
Control typePush-button
Main product or component typeSwitch disconnector
Voltage690 V AC 50/60 Hz conforming to IEC 60947-3
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-3
CurrentAC-23 A: 1250 A AC 50/60 Hz 690 V
Utilization categoryAC-23 A
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-5 °C

All specifications

ENW24279 additional specifications
ParameterValue
Storage temperature-40...85 °C without control unit
Pollution degree4 conforming to IEC 60664-1
Depth395 mm
Width556 mm
Height439 mm
ApplicationDistribution
Operating temperature-5...70 °C

Product details

Switch disconnector for distribution — 1250 A, drawout, isolation-rated

The ENW24279 is a Schneider Electric EasyPact NW switch disconnector rated for 1250 A in AC-23A duty at 690 V AC, 50/60 Hz. That AC-23A utilisation category means it handles switching of mixed motor and resistive loads — not just isolation — with an electrical durability of 6000 cycles at 440 V and 4000 cycles at 690 V without maintenance, per IEC 60947-3. Four-pole configuration with neutral on the right, drawout mounting on a rail, and rear connection terminals on a 115 mm pitch without spreader. The drawout mechanism lets you rack the disconnector out for maintenance or replacement without disturbing the power wiring — a time-saver in panel retrofits. Rated for isolation per IEC 60947-3 — the contact position indicator gives visual confirmation of open/closed state, which matters for lockout/tagout procedures.

Fault-handling and duty ratings

Short-time withstand current (Icw) is 66 kA for 1 second, or 36 kA for 3 seconds, at ambient temperatures from -5 to 70 °C. That 66 kA/1 s rating tells you the disconnector can ride through a bolted fault long enough for an upstream breaker to clear — critical for selective coordination studies. Rated short-circuit making capacity (Icm) is 143 kA peak at 50/60 Hz. Mechanical durability is 20,000 cycles with maintenance or 10,000 cycles without maintenance per IEC 60947-3. The continuous duty rating means it's designed for uninterrupted current-carrying at the full 1250 A — not just occasional switching.

IP40 protection — suitable for indoor switchgear enclosures where tools and fingers are the main ingress concern, not washdown or outdoor exposure. Breaking capacity code HA and the 143 kA making capacity mean this is the high-amperage variant in the EasyPact NW range — sized for main incoming or heavy feeder duty, not branch-circuit sub-feeders.

MPN
ENW24279