Schneider Electric EZC100H4100 EasyPact EZC100H 100A 4P MCCB

MPN EZC100H4100
Active

Schneider Electric EasyPact EZC100H series, EZC100H4100, 4-pole MCCB, 100 A thermal-magnetic TM-D trip unit, 10–100 kA Icu breaking capacity, IEC 60947-2.

$76.41 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

EZC100H4100 key specifications
ParameterValue
Control typeToggle
Network typeDC AC
Trip unit typeThermal-magnetic
Main product or component typeCircuit breaker
Voltage550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Insulation voltage ui690 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP20
Terminal pitch25 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-35 °C

All specifications

EZC100H4100 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-35...85 °C
Pollution degree3 conforming to IEC 60947
Depth60 mm
Width100 mm
Height130 mm
Mechanical life cycles13000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The EZC100H4100 is a 4-pole moulded-case circuit breaker from the Schneider Electric EasyPact EZC100H series, rated 100 A at 40 °C with a TM-D thermal-magnetic trip unit. The H breaking capacity code tells you the interrupting rating at the highest-voltage test point: 100 kA Icu at 110–130 V AC, 30 kA at 380–400 V AC, and 10 kA at 550 V AC. The 4-pole configuration with 3t protected poles and no neutral protection means the breaker protects three phases and switches the neutral without a trip element on it — standard for a 3-phase + N distribution board where the neutral is not expected to carry fault current. The 690 V AC rated insulation voltage and 550 V AC maximum operational voltage cover 400/480 V systems with headroom, and the 250 V DC rating makes it usable in DC distribution panels up to that voltage.

Deployment context

The breaker mounts fixed to a backplate with a 25 mm connection pitch — standard for panelboard or switchboard integration. The IP20 degree of protection means it is suitable for installation inside a closed electrical enclosure where no water ingress is expected; the IK07 impact rating provides basic mechanical robustness against accidental tool strikes during panel wiring.

It also carries JIS C8201-2-2 and GB/T 14048.2 approvals, covering Japanese and Chinese markets respectively. Pollution degree 3 allows installation in environments with conductive pollution (condensation, light dust), typical of industrial control panels not in a climate-controlled room.