Skip to main content
Schneider Electric EZC100H4100 — Circuit Breaker Accessories

Schneider Electric EZC100H4100 EasyPact EZC100H 100A 4P MCCB

MPNEZC100H4100
Active

Schneider Electric EasyPact EZC100H series, EZC100H4100, 4-pole MCCB, 100 A thermal-magnetic TM-D trip unit, 10–100 kA Icu breaking capacity, IEC 60947-2.

$76.41Ref. price · indicative, final on quote
StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

EZC100H4100 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution

Electrical

EZC100H4100 — Electrical
ParameterValue
Network type (AC/DC)DC AC
Rated current [In]100 A at 40 °C
Rated operational voltage [Ue]550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description4P

Protection & Performance

EZC100H4100 — Protection & Performance
ParameterValue
Breaking capacity10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]5 kA at 125 V DC conforming to IEC 60947-2 5 kA at 250 V DC conforming to IEC 60947-2 5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
Trip unit technologyThermal-magnetic
Trip unit rating100 A at 50 °C
Trip unit nameTM-D
Protection typeOverload protection Short-circuit protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability13000 cycles
Local signallingPositive contact indication

Mechanical

EZC100H4100 — Mechanical
ParameterValue
Connection pitch25 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC100H
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width100 mm
Height130 mm
Depth60 mm

Environmental

EZC100H4100 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Pollution degree3 conforming to IEC 60947
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C

Approvals

EZC100H4100 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 JIS C8201-2-2 GB/T 14048.2

Product details

The EZC100H4100 is a 4-pole moulded-case circuit breaker from the Schneider Electric EasyPact EZC100H series, rated 100 A at 40 °C with a TM-D thermal-magnetic trip unit. The H breaking capacity code tells you the interrupting rating at the highest-voltage test point: 100 kA Icu at 110–130 V AC, 30 kA at 380–400 V AC, and 10 kA at 550 V AC. The 4-pole configuration with 3t protected poles and no neutral protection means the breaker protects three phases and switches the neutral without a trip element on it — standard for a 3-phase + N distribution board where the neutral is not expected to carry fault current. The 690 V AC rated insulation voltage and 550 V AC maximum operational voltage cover 400/480 V systems with headroom, and the 250 V DC rating makes it usable in DC distribution panels up to that voltage.

Deployment context

The breaker mounts fixed to a backplate with a 25 mm connection pitch — standard for panelboard or switchboard integration. The IP20 degree of protection means it is suitable for installation inside a closed electrical enclosure where no water ingress is expected; the IK07 impact rating provides basic mechanical robustness against accidental tool strikes during panel wiring.

It also carries JIS C8201-2-2 and GB/T 14048.2 approvals, covering Japanese and Chinese markets respectively. Pollution degree 3 allows installation in environments with conductive pollution (condensation, light dust), typical of industrial control panels not in a climate-controlled room.

Frequently asked questions

Where can I buy EZC100H4100 and get a price?

The EZC100H4100 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead-time estimate.

What is the breaking capacity of EZC100H4100 at 400 V?

At 380–400 V AC 50/60 Hz, the EZC100H4100 delivers 30 kA Icu per IEC 60947-2. This is the maximum fault current the breaker can safely interrupt at that voltage level.

What compliance documentation does EZC100H4100 carry?

The breaker is certified to EN/IEC 60947-1, EN/IEC 60947-2, JIS C8201-2-2, and GB/T 14048.2. It is suitable for isolation per IEC 60947-2 and carries IP20 and IK07 protection ratings.

MPN
EZC100H4100