Skip to main content
Schneider Electric EZC630N3600N

Schneider Electric EZC630N3600N EasyPact EZC630N, 630 A, 36

MPN EZC630N3600N
Active

Schneider Electric EasyPact EZC630N, circuit breaker, 630 A at 40 °C, 36 kA Icu at 440 V AC, thermal-magnetic TM-D trip unit, 3 poles, IP20.

$495.47 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

EZC630N3600N key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeCircuit breaker
Voltage440 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui690 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP20
Terminal pitch45 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-35 °C
Temp operating max70 °C

All specifications

EZC630N3600N additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-35...85 °C
Pollution degree3 conforming to IEC 60947
ColorBlack
Depth110 mm
Width140 mm
Height255 mm
Electrical life cyclesCategory A: 3000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical life cycles10000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

630 A thermal-magnetic breaker, 36 kA at 440 V — panel fit and protection

The Schneider Electric EZC630N3600N is a 3-pole EasyPact EZC630N circuit breaker rated 630 A at 40 °C with a thermal-magnetic TM-D trip unit. Its 36 kA Icu at 440 V AC (50/60 Hz) per IEC 60947-2 means it can safely interrupt faults up to that level without cascading upstream — a key number for the site electrical engineer checking SCCR headroom and selectivity coordination. Mounts fixed to a backplate (not DIN rail), with front-front connections and a 45 mm pole pitch. The IP20 enclosure and IK07 impact rating suit it for enclosed panel installation where personnel access is controlled.

Trip unit and protection characteristics

The TM-D thermal-magnetic trip unit provides overload and short-circuit protection. Magnetic tripping current is 5000 A. Mechanical durability is 10000 cycles; electrical durability is 3000 cycles at 415 V AC. No earth-leakage or neutral protection built in.

MPN
EZC630N3600N