Schneider Electric EasyPact EZC630N, circuit breaker, 630 A at 40 °C, 36 kA Icu at 440 V AC, thermal-magnetic TM-D trip unit, 3 poles, IP20.

$495.47Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

EZC630N3600N — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC630N3600N — Electrical
ParameterValue
Network type (AC/DC)AC
Rated current [In]630 A at 40 °C
Rated operational voltage [Ue]440 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description3P
EZC630N3600N — Protection & Performance
ParameterValue
Breaking capacity36 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]18 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN
Trip unit technologyThermal-magnetic
Trip unit rating600 A at 50 °C
Trip unit nameTM-D
Protection typeOverload protection Short-circuit protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability10000 cycles
Electrical durabilityCategory A: 3000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
Local signallingPositive contact indication
Contact position indicatorYes
EZC630N3600N — Mechanical
ParameterValue
Connection pitch45 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC630N
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width140 mm
Height255 mm
Depth110 mm
ColourBlack
EZC630N3600N — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Pollution degree3 conforming to IEC 60947
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC630N3600N — Approvals
ParameterValue
StandardsEN/IEC 60947-2 GB/T 14048.2 JIS C8201-2-2 EN/IEC 60947-1

Product details

630 A thermal-magnetic breaker, 36 kA at 440 V — panel fit and protection

The Schneider Electric EZC630N3600N is a 3-pole EasyPact EZC630N circuit breaker rated 630 A at 40 °C with a thermal-magnetic TM-D trip unit. Its 36 kA Icu at 440 V AC (50/60 Hz) per IEC 60947-2 means it can safely interrupt faults up to that level without cascading upstream — a key number for the site electrical engineer checking SCCR headroom and selectivity coordination. Mounts fixed to a backplate (not DIN rail), with front-front connections and a 45 mm pole pitch. The IP20 enclosure and IK07 impact rating suit it for enclosed panel installation where personnel access is controlled.

Trip unit and protection characteristics

The TM-D thermal-magnetic trip unit provides overload and short-circuit protection. Magnetic tripping current is 5000 A. Mechanical durability is 10000 cycles; electrical durability is 3000 cycles at 415 V AC. No earth-leakage or neutral protection built in.

Frequently asked questions

What are the key ratings of EZC630N3600N?

Rated 630 A at 40 °C, breaking capacity 36 kA Icu at 440 V AC, thermal-magnetic TM-D trip, 3 poles, IP20.

MPN