Skip to main content
Schneider Electric GC2502E5

Schneider Electric GC2502E5 TeSys GC Modular Contactor, 48 V

MPN GC2502E5
Obsolete

Schneider Electric TeSys GC modular contactor, GC2502E5, 2-pole, 48 V AC 50 Hz control, AC-7A/AC-7B utilisation, DIN-rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

GC2502E5 key specifications
ParameterValue
Control typeRemote control
Control circuit typeAC at 50 Hz
Main product or component typeModular contactor
Voltage<= 250 V AC
Coil voltage48 V AC 50 Hz
Insulation voltage ui500 V conforming to IEC 61095 500 V conforming to VDE 0110
Current25 A AC-7 A 8.5 A AC-7B
Breaking capacity68 A at 400 V for power circuit conforming to IEC 61095
Utilization categoryAC-7 A AC-7B
Temp storage max70 °C
Temp storage min-40 °C
Temp operating max50 °C

All specifications

GC2502E5 additional specifications
ParameterValue
Temp operating min-5 °C
Storage temperature-40...70 °C
ColorWhite
Depth62.5 mm
Width17.5 mm
Height81 mm
Electrical life cyclesAC-7 A: 100000 cycles AC-7B: 100000 cycles
Mechanical life cycles1000000 cycles
ApplicationLighting Heating Motor control
Operating time10...25 ms opening 10...30 ms closing
Operating position30°/vertical
Operating temperature-5...50 °C

Product details

The contactor clips onto a standard DIN rail, occupying a single 18 mm module width, which keeps panel layout dense and predictable for a 2-pole device.

The 48 V AC 50 Hz coil pulls 15 VA inrush at 20 °C and dissipates 1.3 W holding power — a modest draw that a small control transformer can support, but the drop-out threshold of 0.2...0.75 Uc means the coil releases reliably even on a sagging line, which matters for undervoltage protection schemes. Electrical durability is 100,000 cycles for both AC-7A and AC-7B duty; mechanical durability is 1,000,000 cycles. For a lighting or small-motor application cycling a few times per hour, that translates to years of service before a planned replacement. Operating time is 10...25 ms opening and 10...30 ms closing — fast enough for most switching sequences, but not a high-speed transfer switch. The maximum operating rate is 300 cycles per hour at 50 °C.

The 17.5 mm width and 81 mm height let it slot into a standard 18 mm DIN-rail grid alongside other TeSys GC modular devices — breakers, timers, auxiliary contact blocks — without wasting rail space. Screw-clamp terminals on both control and power circuits accept up to 6 mm² solid or flexible cable on the power side, which is adequate for the 25 A fuse rating. Torque to 0.8 N·m on all terminals.

MPN
GC2502E5