Skip to main content
Schneider Electric LC1F4004V7

Schneider Electric LC1F4004V7 TeSys F Contactor, 500 A AC-1,

MPN LC1F4004V7
Obsolete

Schneider Electric TeSys F contactor, LC1F4004V7, 4-pole NO, 500 A AC-1 rated operational current, 400 V AC 50/60 Hz coil, plate-mount, end-of-life.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LC1F4004V7 key specifications
ParameterValue
Control circuit typeAC at 40...400 Hz
Main product or component typeContactor
Voltage<= 460 V DC
Coil voltage400 V AC 40...400 Hz
Insulation voltage ui1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C
Current500 A (at <40 °C) at <= 440 V AC AC-1
Breaking capacity3200 A conforming to IEC 60947-4-1
Utilization categoryAC-1
Temp storage max80 °C
Temp storage min-60 °C
Temp operating max55 °C
Temp operating min-5 °C

All specifications

LC1F4004V7 additional specifications
ParameterValue
Storage temperature-60...80 °C
Depth219 mm
Width261 mm
Height206 mm
Mechanical life cycles10 Mcycles
ApplicationResistive load
Operating time40...65 ms closing 100...170 ms opening
Operating temperature-5...55 °C
Permissible ambient air temperature around the device-40...70 °C

Product details

TeSys F 4-Pole Contactor, 500 A AC-1 — End-of-Life Sourcing Note

The Schneider Electric LC1F4004V7 is a TeSys F 4-pole contactor rated 500 A in AC-1 utilisation category (resistive load) at ≤ 440 V and ≤ 40 °C. The 400 V AC coil draws 1075 VA inrush, holding at 15 VA. This is a plate-mount device — no DIN-rail adapter — sized for bolted busbar or lug connections up to 150 mm² per pole.

The 500 A AC-1 rating governs resistive loads like heaters or large lighting banks. For motor duty (AC-3), the contactor would derate significantly — verify against the motor full-load current. The 400 V AC coil operates from 0.85 to 1.1 Uc (340–440 V) and drops out between 0.3 and 0.5 Uc (120–200 V). The 4 NO poles are all normally open; no NC auxiliary is built in, so plan for an external aux block if needed.

Certified to IEC 60947-4-1, EN 60947-4-1, IEC 60947-1, EN 60947-1, and JIS C8201-4-1. Rated insulation voltage 1000 V per IEC 60947-4-1 (1500 V per VDE 0110 group C). Impulse withstand voltage 8 kV, overvoltage category III.

Mounting and Connection

Plate-mount only — no DIN-rail option. Dimensions 261 mm wide × 206 mm high × 219 mm deep. Power connections accept bolted busbar (30 × 5 mm) or lug-ring terminals up to 150 mm². Control circuit uses screw-clamp terminals accepting 1–4 mm² flexible or solid. Tightening torque: 35 N·m on power circuit, 1.2 N·m on control circuit.

MPN
LC1F4004V7